How to perform placement, anchor, and prewire
procedures for installation of the first or second
EZBFo battery base modules
.............................................................................................................................................................................................................................................................
Overview
Purpose Important! If installing a EZBFo battery add-on module only, proceed
to How to install an EZBFo battery add-on module on an existing EZBFo
battery module on Page A - 76 to continue the installation. If installing
an EZBFo battery base module, continue as instructed.
This section describes the procedures for placement, anchoring, and
prewiring of the first or second EZBFo battery base modules.
Instructions are given for right-hand (primary cabinet) installation.
Left hand installation (4.0B Dual Band cabinet) is the same except for
the routing of the cables into and through the 4.0B Dual Band cabinet.
This alternate routing is provided.
.............................................................................................................................................................................................................................................................
Anchor and hole size requirements
Anchor hole size
requirements for the
EZBFo battery base
module
The following table provides anchor type and hole size requirements
for the EZBF0 battery base module.
* A EZBFo battery frame installed in Zone 4 can be installed with only
one add-on module unless a zone 4 mounting kit is installed at the time
of the addition of the second add-on module.
Anchor hole size requirements for the EZBFo battery base module A - 8
How to place and attach the EZBFo battery base module outer frame
and mark, drill, and set anchors
A - 9
How to install the battery heater pad kit in an EZBFo battery module A - 19
How to install the inner battery frame and level, anchor, and ground the
first or second EZBFo battery base modules
A - 27
Seismic
Zone(s)
Anchor Quantity/Type Hole Size / Depth
0, 1, and 2 (4) 1/2" dia. drop in 5/8" bit / 2" (50 mm) deep
3 and 4* (8) 1/2" dia. drop in 5/8" bit / 2" (50 mm) deep