User's Manual

A- 32
Lucent Technologies – Proprietary
See notice on first page
401-703-454
FOA Draft Issue 1
January, 2006
...........................................................................................................................................................................................................................................................
Level and anchor the
battery base module
Important! If installing an add-on module, return to Attach the
internal ground cable between the add-on module and the module below
it on Page A - 83 to continue the installation.
Use the following procedure to level and anchor the battery base
module and attach the internal ground cable.
1 Align the battery base module inner frame and outer frame mounting
holes with the anchor holes or anchors, as applicable.
Seismic Zones 0, 1, and 2: Over the four installed anchors
Seismic Zones 3 and 4: Over the eight installed anchors.
Important! When performing the next step, do not tighten the
anchor bolts until the battery base module has been leveled in the
following step.
................................................................................................................................
............................................
2 Insert the four or eight anchor bolts, as applicable, with two washers
each but leave loose. Refer to the figure below.
INNER
FRAME
B
OTTOM PLATE
O
F OUTER FRAME
ANCHOR BOLT
LOCATION "A"
(2 each side)
ANCHOR BOLT
LOCATION "B"
(2 each side)
THE OUTER
B
ATTERY FRAME
I
S NOT SHOWN
F
OR CLARITY