User's Manual

A- 52
Lucent Technologies – Proprietary
See notice on first page
401-703-454
FOA Draft Issue 1
January, 2006
...........................................................................................................................................................................................................................................................
Install the fuse, the fuse
alarm actuator and the fuse
alarm switch in the first
battery base module
Perform the following steps to install the fuse, fuse alarm actuator and
fuse alarm switch in the first battery base module. Use the hardware
supplied on the bus bars.
................................................................................................................................
............................................
1 Attach the fuse between the upper and lower return bus bars which are
mounted on the inside front left side of the outer frame. Refer to the
figure below. The fuse rating will vary depending upon the application.
................................................................................................................................
............................................
2 Attach the fuse alarm actuator between the upper and lower return bus
bars next to the fuse.
................................................................................................................................
............................................
3 Mount the fuse alarm switch on the top of the actuator with the spade
lugs pointing down.
................................................................................................................................
............................................
4 Torque all connections to 28Nm (250 in.-lb.).
FRONT
S
IDE VIEW
FUSE ALARM
ACTUATOR
FUSE ALARM
ACTUATOR AND
SWITCH
FUSE ALARM
SWITCH
(SPADE LUGS
DOWN)
RTN2
RTN1
FRONT V
IE
W
FUSE