How to route and connect the DC cables in the first battery base
.............................................................................................................................................................................................................................................................
module
Overview
Important! DC cables must be individually taped in the Modular Cell
cabinet at this time
This procedure module provides instructions for the routing and
connection of the eight 2 AWG DC power cables (four +24V DC load
and four 24V Return) from the Modular Cell cabinet, in the first
EZBFo battery base module.
Step-by-step instructions are provided for the following tasks
Description of DC power cable routing and connection
The first battery base module requires eight 2 AWG DC power cables
from the Modular Cell cabinet: Four +24V DC load cables (+) and four
24V Return cables (-). These cables are terminated with two hole
terminal lugs on the first battery base module end and unterminated on
the Modular Cell end.
Route and connect the four +24V DC load cables in the battery
base module
A - 58
Route and connect the four 24V Return cables in the battery
base module
A - 60