User's Manual

The following figure shows the drill pattern for the floor stand anchor holes.
Mark and drill the anchor holes
Important! The marking and drilling of the anchor holes shall be performed as part of
site preparation. Anchor holes must be properly covered to prevent debris from falling
inside. Before marking or drilling the anchor holes, refer to
“RRH clearances”
(p. 5-4)
for more details.
Proceed as follows to mark and drill the anchor holes in a concrete surface:
...................................................................................................................................................................................................
1
Measure and mark the location where the RRH anchors will be installed. Refer to “RRH
clearances” (p. 5-4)
and the figure above for anchor footprint.
...................................................................................................................................................................................................
2
Drill the anchor holes to the proper size and depth as specified in the previous table.
Important! If a 100 mm (4.00”) hole depth cannot be attained for a 12-mm expansion
stud anchor, a spacer may be removed from the anchor assembly when it is installed.
The minimum depth of the hole is 76.2 mm (3.00”).
...................................................................................................................................................................................................
3
If Then
floor stand is not available on site tape over the open holes to prevent debris
from falling inside.
do not install the anchors at this time. Anchors
will be installed later by equipment installers.
procedure ends here.
floor stand is available on site continue with next step.
Site requirements Site requirements for floor stand installations
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
5-14
Alcatel-Lucent Proprietary
Use pursuant to applicable agreements
Alcatel-Lucent RRH 2X60W
NN-20500-305 UA08.1
Issue 0.7 November 2011