User's Manual

5-4
5.3
SPECIAL TOOLS
Refer to Table 5-1 for special tools required for maintenance. Similar tools can be substi-
tuted for those recommended; however, before substitution, check the minimum parameters.
5.4
PERSONAL COMPUTER (PC)
The PC is an on-line maintenance and troubleshooting tool. See Figure 5-2. Connect the
RS-232 interface cable between USI connector on controller and the PC.
5.5
ALARM MONITORING AND INSPECTION
Perform the following checks whenever a station is entered:
1
Verify that no alarms are lighted; only the green status indicators should be
lighted.
2
Momentarily press LAMP TEST switch. Verify all indicators light.
Keeping records of errors and alarm history can be an aid to system trouble-
shooting.
The local status alarms screen displays the alarms of the radio to which the
USI is connected, either physically or addressed via the ELMC.
3
Using the USI computer, check local alarms on the Local Status Alarms
screen.
Table 5-1 Special Tools Required
TOOL ESSENTIAL CHARACTERISTICS USED ON
Torque Limiting Screwdriver
Briggs-Weaver PN 8370-01880
#2 Phillips, 19 in-lb DS1/E1, DS3, OC3
#2 Phillips Bit Extension
Briggs-Weaver PN 8528-27370
(for use with torque limiting screw-
driver)
DS1/E1, DS3, OC3
Torque Wrench,
Utica Model CHA5 w/OP-102
5/16 in., 7-to-9 in-lb, sensing type DS1/E1, DS3, OC3
Note
Note