Service manual

16
5:0 SAFETY CHECK
The safety check must be carried out after every service.
Check:
That the intake/exhaust hoses and ue are tight and
undamaged.
That the LPG pipes are tight. Pressure test the system.
That the 230 V~ earth cable is connected.
That the safety valve on the water heater is not blocked.
That the heating system is lled with glycol mixture
up to the mark on the expansion vessel.
Fig 28.
A
White
Red
Blue
4:10 REPLACING THE PRESSURE SWITCH
1. Remove the cover and end-plate from the boiler.
2. Detach the blue, white and red cables on the pressure
switch.
3. Push back the metal securing plate and pull out the
pressure switch (g. 28 A).
4. Detach the rubber hoses (g. 28 B) from the pressure
switch (do not pull the hoses, unscrew them).
5. Ret the hoses to the new pressure switch before
pushing it into place.
6. Fasten the pressure switch and t the cables to the at-
pin contacts in accordance with g. 28.
7. Fit the cover and end plate to the boiler. Test-start the
boiler.
B