WAB-WYB SERIES SINGLE SPLIT DC INVERTER AIR CONDITIONER / HEAT PUMP SYSTEMS Mono DC SERVICE MANUAL COVERING 16 SEER and 20 SEER FAMILY OF WAB-WYB MODELS Parker Davis HVAC International, Inc. Revision A: 1312030001, Content updated. Cooling Only Model Numbers (Indoor + Outdoor Units): 2260 NW 102nd Place, Doral, FL 33172 Ph: (305) 513-4488 info@pd-hvac.
CONTENTS 1. Precaution ................................................................................................................................................. 1 1.1 Safety Precaution ........................................................................................................................ 2 1.2 Warning ....................................................................................................................................... 3 2. Part Names And Functions .................
Sharp edges could cause injury, be especially careful of the case edges and the fins on the condenser and evaporator. 1. Precaution For installation, always contact the dealer or an authorized service center. Do not install the product on weak or defective structures or stands. Be sure the installation area does not deteriorate with age. If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury. 1.
There is risk of electric shock or fire. product. To avoid vibration of water leakage. Stop operation and disconnect the power during storm or hurricane. If possible, further secure the product before the hurricane arrives. There is risk of property damage, failure of product, or electric shock. Do not install the product where the noise or hot air from the outdoor unit could disturb the neighbors. It may cause disturbance for your neighbors.
Use a firm stool or ladder when cleaning or maintaining the product. Be careful and avoid personal injury. Replace the all batteries in the remote control with new ones of the same type. Do not mix old and new batteries or different types of batteries. There is risk of fire or explosion. Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire. They may burn of explode. If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water.
2. Part Names And Functions 2.
2.
3. Dimension 3.1 Indoor Unit H D W Model W D H WB009GMFI16HLD 790mm (31.1in) 198mm (7.8in) 265mm (10.43in) 920mm (36.22in) 223mm (8.78in) 292mm (10.5in) 998mm (39.29in) 240mm (9.45in) 322mm (12.
L R H Model R L H Dimension of installation hole WB024GMFI20CLD WB024GLFI20HLD 150mm (5.91in) 100mm (3.94in) 45mm (1.77in) Φ65mm (2.56in) Model R L H Dimension of installation hole 185mm (7.28in) 150mm (5.91in) 45mm (1.77in) Φ65mm (2.
Model R L H Dimension of installation hole 120mm (4.72in) 100mm (3.94in) 45mm (1.77in) Φ65mm (2.
Model W D H 1450mm (57.1in) 265mm (10.43in) 340mm (10.
3.2 Outdoor Unit More than 30cm(11.8in) More than 30cm(11.8in) More than 60cm(23.6in) ︶ (Service space Fe n ob ce o s ta r cle s More than 60cm(23.6in) More than 70cm(27.6in) Note: The above drawing is only for reference. The appearance of your units may be different. Model W D H W1 A B AN009AMFI20RPD YN009AMFI20HLD YN009GMFI16RPD AN012GMFI16RPD 760mm 285mm 590mm 823mm 530mm 290mm (29.9in) (11.2in) (23.2in) (32.4in) (20.9in) (11.
4. Refrigerant Cycle Diagram For cooling only models: INDOOR OUTDOOR LIQUID SIDE T3 Condenser temp. sensor CAPILIARY TUBE HEAT EXCHANGE (EVAPORATOR) T1 Room temp. sensor T4 Ambient temp. sensor T2 Evaporator temp. sensor T5 Discharge temp.
For heat pump models: INDOOR OUTDOOR CHECK VALVE (Heating Model only) LIQUID SIDE 2-WAY VALVE T3 Condenser temp. sensor CAPILIARY TUBE HEAT EXCHANGE (EVAPORATOR) HEAT EXCHANGE (CONDENSER) T4 Ambient temp. sensor T1 Room temp. sensor T2 Evaporator temp. sensor GAS SIDE 4-WAY VALVE 3-WAY VALVE Accumulator Compressor T5 Discharge temp.
5. Wiring Diagram 5.
9000 BTU-12000BTU, 115V, 20 SEER, Cool Only and Heat Pump 14
12000 BTU, 115 VAC, 20 SEER, Heat Pump 15
12000 BTU, 230V, 20 SEER Cool Only and Heat Pump 16
18000 BTU, 20 SEER, Heat Pump 17
18000 BTU / 24000 BTU, 16 SEER Heat Pump 18
24000 BTU, 20 SEER, Cool Only and Heat Pump 19
5.
9000 BTU, 115V, 20 SEER Cool Only / 12000 BTU, 115V, 20 SEER Heat Pump 21
12000 BTU, 230V, 20 SEER, Cool Only and Heat Pump 22
9000 BTU, 115V, 20 SEER Heat Pump / 12000 TU, 115V, 20 SEER Cool Only and Heat Pump 23
18000 BTU, 16 AND 20 SEER, Heat Pump 24
18000 BTU and 24000 BTU, 16 SEER, Heat Pump 25
24000 BTU, 20 SEER, Cool Only and Heat Pump 26
For 9000 BTU and 12000 BTU, 115 V, 20 SEER, Cool Only and Heat Pump 27
For 9000 BTU and 12000 BTU, 230V, 16 SEER, Heat Pump, 28
For 12000 BTU, 230 V, 20 SEER, Cool Only 29
For 12000 BTU and 18000 BTU, 230 V, 20 SEER, Heat Pump 30
For 12000 BTU, 230 V, 20 SEER, Heat Pump 31
For 18000 BTU, 16 SEER, Heat Pump 32
For 18000 BTU and 24000 BTU, 16 SEER, Heat Pump 33
For 24000 BTU, 20 SEER, Heat Pump 34
6.3 Pipe length and the elevation 6 Installation Details Pipe size 6.1 Wrench torque sheet for installation Outside diameter Models torque Ф6.35mm 1/4in 1500N.cm (11 Lbf.Ft). 1600N.cm (12 Lbf.Ft.) Ф9.52mm 3/8in 2500N.cm (18 Lbf.Ft.) 2600N.cm (19 Lbf.Ft) Ф12.7mm 1/2in 3500N.cm (26 Lbf.Ft) Ф15.9mm 5/8in 4500N.cm (33 Lbf.Ft) WB009AMFI20CLD+AN009AMFI20RPD WB009AMFI20HLD+ YN009AMFI20HLD 3600N.cm (27 Lbf.Ft) WB009GMFI16HLD+ YN009GMFI16RPD 3/4in Liquid 3/8in 1/4in (Ф9.52mm) (Ф6.
Max. Standard Additional Max.
5) Operate the vacuum pump to evacuate. 6) Make evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa(14.5Psi). If the meter does not indicate -0.1Mpa(14.5Psi) after pumping 30 minutes, it should be pumped 20 minutes more. If the pressure can’t achieve -0.1Mpa(14.5Psi) after pumping 50 minutes, please check if there are some leakage points. Fully close the Low side valve of the manifold and stop the vacuum pump.
2). Purge the air from the charge hose. Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant). 3) Put the charging cylinder onto the electronic scale and record the weight. 4) Operate the air conditioner at the cooling mode. 5) Open the valves (Low side) on the charging manifold set and charge the system with liquid refrigerant. 6).
manifold hose with the push pin to the 3-way valve's gas service port. 3). Air purge of the charge hose. Open the Low side valve of the manifold slightly to purge air from the charge hose for 5 seconds and then close it quickly. 4). Set the 2-way valve to the close position. 5). Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1Mpa(14.5Psi). 6). Set the 3-way valve to the closed position immediately Do this quickly so that the gauge ends up indicating 0.3Mpa(43.
2. Refrigerant charging Procedure: 1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder upside down to ensure liquid charge. 2).
7.
8. Electronic Function 8.1 Abbreviation T1: Indoor room temperature T2: Coil temperature of evaporator T3: Coil temperature of condenser T4: Outdoor ambient temperature T5: Compressor discharge temperature 8.2 Display function 8.2.1 Icon explanation on indoor display board. ION indication lamp (optional function):This lamp illuminates when Clean Air feature is activated.
8.3 Main Protection 8.3.1 Three minutes delay at restart for compressor 1 minute delay for the 1st time start-up and 3 minute delay for subsequent starts. 8.3.2 Temperature protection of compressor top surface. The unit will stop working when the compressor top temp. protector activates, and will restart after the compressor top temp. protector resets. 8.3.3 Temperature protection of compressor discharge pipe When the compressor discharge temp.
8.4 Operation Modes and Functions 8.4.1 Fan mode Fmax=F4 45 8.4.1 Fan only mode (1) Outdoor fan and compressor stop. (2) Temperature setting function is disabled, and no set temperature is displayed. (3) Indoor fan can be set to high/med/low/auto. (4) The louver operates same as in cooling mode. (5) Auto fan: 43 Fmax=F7 40 38 Fmax=F8 31.5 29.5 For 9000 BTU, 12000 BTU and 18000 BTU, 20 SEER Cool Only and Heat Pump models: Fmax=F6 22 20 T1-24 Fmax=F3 6.0 5.0 4.0 2.5 1.0 H a (H-L)*0.75+L (H-L)*0.
Note: When T1-Ts stays in the same temp. zone for 3 minutes, the compressor will run as the below rules: A~E: Increase the frequency to the higher level until reaching F8. F: Keep the current frequency. G: Decrease the frequency to the lower level until reaching F1. H: Run at F1 for 1h. (if T1-Ts<-2℃, the compressor will stop) Meanwhile, the compressor running frequency is limited by the current.
For other models, when the compressor is running, the indoor fan will run at setting fan speed. When the setting temp. is reached, the 34 33 indoor fan will run at lowest fan speed. 28 27 Auto fan running rules: For 9000 BTU, 12000 BTU and 18000 BTU, 20 SEER Cool Only and Heat Pump models: Off Fmax=F2 25 24 Fmax=F3 22 21 Fmax=F4 19 18 Fmax=F5 17 16 Fmax=F6 15 14 Fmax=F7 12 11 Fmax=F8 6 5 Fmax=F9 T1-Ts 6.0 5.0 4.0 2.5 1.0 H a b c d e (H-L)*0.75+L (H-L)*0.5+L (H-L)*0.
Decrease: Decrease the running frequency to the lower level. Hold: Keep the current frequency. Resume: No limitation for frequency. H H +5.0 Note: When AC is in “hold” zone for 3 minutes, the compressor frequency will rise to the higher level. (The frequency will increase twice at most) +4.5 G +3.5 +3.0 F +2.5 E +2.0 D 8.4.3.2 Outdoor fan running rules For 9000 BTU, 12000 BTU and 18000 BTU, 20 SEER Cool Only and Heat Pump models: C +1.5 B +1.0 +0.5 Heating A While the zones of A,B,C...
For 9000 BTU, 12000 BTU, 20 SEER Cool Only and Heat Pump models, the anti-cold (Warm Start) function is as below for : T1-Ts+¦ ¤ T 0.0 -1.0 T2 44 L (H+-L)*0.2+L (H+-L)*0.4+L -2.0 -3.0 Setting (H+-L)*0.6+L -4.0 (H+-L)*0.6+L -5.0 -6.0 -6.5 38 37 Low (H+-L)*0.8+L H+ 34 33 Breeze TEL1 TEL0 For other models: Super Breeze T1-Ts Off Low For other models: 2.5 2.0 Medium 1.5 44 1.0 Setting High 38 37 8.4.3.
than 5℃ or not. Frequency F2 Frequency F8 Condition of ending defrosting: If any one of the following items is satisfied, the defrosting will end and the machine will turn to normal heating mode. ----T3 rises to be higher than TCDE1℃. ----T3 stays to be higher than TCDE2℃ for 80 seconds. ----The machine has run for 10 minutes in defrosting mode.
and cooling, the compressor will keep stopping for 15 minutes and then choose mode according to T1-Ts. If the setting temperature is modified, the machine will choose running function again. 8.4.6.3 Operation rules: Forced cooling mode: The compressor runs at F2 frequency and indoor fan runs as breeze. After running for 30 minutes. the machine will turn to auto mode as 24℃ setting temperature. Forced auto mode: The action of forced auto mode is the same as normal auto mode with 24℃ setting temperature. 8.
temperature stops rising and indoor fan is fixed as low speed. (Warm-Start function has the priority) 8.4.8.3 Timer setting is available 8.4.8.4 When user uses timer off function in sleep mode (or sleep function in timer off mode), if the timing is less than 7 hours, sleep function will be cancelled when reaching the setting time. If the timing is more than 7 hours, the machine will not stop until reaching the set time in sleep mode.
Press the “silence” button on remote controller to initiate SILENCE function. When the Silence function is activated, the compressor running frequency will keep lower than F2 and the indoor unit will bring faint breeze, which will reduce the noise to the lowest level and create a quiet and comfortable room for you.
9.1 Indoor Unit Error Display For All Models, (EXCEPT 18000 BTU, 16 SEER, Heat Pump).
For 18000 BRY, 16 SEER Heat Pump Display LED STATUS E0 Indoor unit EEPROM parameter error E1 Indoor / outdoor units communication error E2 Zero crossing signal detection error(except 3D inverter models) E3 Indoor unit fan speed has been out of control E4 Indoor room temperature sensor open circuit or short circuit E5 Evaporator coil temperature sensor open circuit or short circuit E7 Outdoor unit fan speed has been out of control F1 Outdoor ambient temperature sensor open circuit or short c
9.
For 9000 BTU and, 12000 BTU, 230V, 16 SEER, Heat Pump. After power on, LED1(Blue color) will be slow flash(0.2Hz) when the unit is in standby and quick flash (2.5Hz) if the unit has some problems. No.
For 12000 BTU, 230V, 20 SEER, Cool Only.
For 12000 BTU and 18000 BTU, 230V, 20 SEER, Heat Pump. After power on, LED3(Blue color) will be slow flash(0.2Hz) when the unit is in standby and quick flash (2.5Hz) if the unit has some problems. No.
For 12000 BTU, 230 V, 20 SEER, Heat Pump After power on, LED1(Blue color) will be slow flash(0.2Hz) when the unit is in standby and quick flash (2.5Hz) if the unit has some problems. No.
For 18000 BTU, 16 SEER, Heat Pump After power on, LED3(Blue color) will be slow flash(0.2Hz) when the unit is in standby and quick flash (2.5Hz) if the unit has some problems. No.
For 18000 BTU and 24000 BTU, 20 SEER, Heat Pump After power on, LED1(Blue color) will be slow flash(0.2Hz) when the unit is in standby and quick flash (2.5Hz) if the unit has some problems. No.
For 24000 BTU, 16 SEER, Heat Pump 62
9.3 Diagnosis and Solution 9.3.1 EEPROM parameter error diagnosis and solution(E0/F4) Error Code E0/F4 Malfunction decision Indoor or outdoor PCB main chip does not receive feedback conditions from EEPROM chip. Supposed causes ● Installation mistake ● PCB faulty Trouble shooting: Shut off the power supply and turn it on 5 seconds later. Is it still displaying the error code ? Yes If the EEPROM chip is welded on main PCB, replace the main PCB directly.
9.3.2 Indoor / outdoor unit’s communication diagnosis and solution(E1) Error Code E1 Malfunction decision Indoor unit does not receive the feedback from outdoor unit during conditions 110 seconds and this condition happens four times continuously.
Remark: Use a multimeter to test the DC voltage between L2 (or N for 115V) port and S port of outdoor unit. The red pin of multimeter connects with L2 (or N for 115V) port while the black pin is for S port. When AC is normal running, the voltage will move alternately between -50V to 50V. If the outdoor unit has malfunction, the voltage will move alternately with positive value. While if the indoor unit has malfunction, the voltage will be a certain value.
9.3.3 Zero crossing detection error diagnosis and solution(E2) Error Code E2 Malfunction decision When PCB does not receive zero crossing signal feedback for 4 conditions minutes or the zero crossing signal time interval is abnormal.
9.3.4 Fan speed has been out of control diagnosis and solution (E3/E7/F5) Error Code E3 Malfunction decision When indoor fan speed keeps too low (300RPM) for certain time, conditions the unit will stop and the LED will display the failure.
Index 1: 1.Indoor or Outdoor DC Fan Motor (control chip is in fan motor) Measure the resistance value of each winding by using the tester. If any resistance value is zero, the fan motor must has problems and need to be replaced. Index2: 1:Indoor or Outdoor DC Fan Motor(control chip is in fan motor) Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor connector.
9.3.5 Open circuit or short circuit of temperature sensor diagnosis and solution (E5) Error Code E5 Malfunction decision If the sampling voltage is lower than 0.06V or higher than 4.94 V, conditions the LED will display the failure.
9.3.6 IPM malfunction or IGBT over-strong current protection diagnosis and solution (P0) Error Code P0 Malfunction decision When the voltage signal that IPM send to compressor drive chip conditions is abnormal, the display LED will show “P0” and AC will turn off.
P-U P-V 71
P-W P-N 72
9.3.7 High temperature protection of compressor top diagnosis and solution (P2) Error Code P2 Malfunction decision If the sampling voltage is not 5V, the LED will display the failure. conditions Supposed causes ● Power supply problems.
9.3.8 Inverter compressor drive error diagnosis and solution (P4) Error Code P4 Malfunction decision An abnormal inverter compressor drive is detected by a special conditions detection circuit, including communication signal detection, voltage detection, compressor rotation speed signal detection and so on.
Main parts check 1. Temperature sensor checking Disconnect the temperature sensor from PCB, measure the resistance value with a tester. Temperature Sensors. Room temp.(T1) sensor, Indoor coil temp.(T2) sensor, Outdoor coil temp.(T3) sensor, Outdoor ambient temp.(T4) sensor, Compressor discharge temp.(T5) sensor. Measure the resistance value of each winding by using the multi-meter.
Appendix 1 Temperature Sensor Resistance Value Table for T1,T2,T3,T4 (℃--K) ℃ ℉ K Ohm ℃ ℉ K Ohm ℃ ℉ K Ohm ℃ ℉ K Ohm -20 -4 115.266 20 68 12.6431 60 140 2.35774 100 212 0.62973 -19 -2 108.146 21 70 12.0561 61 142 2.27249 101 214 0.61148 -18 0 101.517 22 72 11.5 62 144 2.19073 102 216 0.59386 -17 1 96.3423 23 73 10.9731 63 145 2.11241 103 217 0.57683 -16 3 89.5865 24 75 10.4736 64 147 2.03732 104 219 0.56038 -15 5 84.
Appendix 2 Temperature Sensor Resistance Value Table for T5 (℃--K) ℃ ℉ K Ohm ℃ ℉ K Ohm ℃ ℉ K Ohm ℃ ℉ K Ohm -20 -4 542.7 20 68 68.66 60 140 13.59 100 212 3.702 -19 -2 511.9 21 70 65.62 61 142 13.11 101 214 3.595 -18 0 483 22 72 62.73 62 144 12.65 102 216 3.492 -17 1 455.9 23 73 59.98 63 145 12.21 103 217 3.392 -16 3 430.5 24 75 57.37 64 147 11.79 104 219 3.296 -15 5 406.7 25 77 54.89 65 149 11.38 105 221 3.203 -14 7 384.
Appendix 3: ℃ ℉ ℃ ℉ ℃ ℉ 10 50 28 84 44 111 11 12 13 50 52 54 29 30 31 86 86 90 45 46 113 115 14 56 32 92 47 117 15 58 33 94 48 118 16 17 18 60 62 64 34 35 36 96 98 98 49 50 120 122 9ΔT 5 ΔT 78 19 66 37 99 20 68 38 100 21 22 23 70 72 74 39 40 102 104 24 76 41 106 25 26 27 78 80 82 42 43 108 109
2.Compressor checking Measure the resistance value of each winding by using the tester. Position Blue - Red Blue - Black Resistance Value DA108X1C-20FZ3 DA150S1C-20FZ DA250S2C-30MT 0.71Ω 0.95Ω 0.
3. IPM continuity check Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital tester to measure the resistance between P and UVWN; UVW and N. Digital tester (+)Red Normal resistance value N P Digital tester (-)Black (+)Red U ∞ U ∞ V (Several MΩ) V N W W Normal resistance value (-)Black (Several MΩ) (+)Red 4: Indoor AC Fan Motor Measure the resistance value of each winding by using the tester.
5: Pressure On Service Port Cooling chart: ℉ (℃) IDT ODT 75 85 95 105 115 (23.89) (29.44) (35) (40.56) (46.11) BAR 70/59 8.2 7.8 8.1 8.6 10.1 BAR 75/63 8.6 8.3 8.7 9.1 10.7 BAR 80/67 9.3 8.9 9.1 9.6 11.2 ℉ (℃) IDT ODT 75 85 95 105 115 (23.89) (29.44) (35) (40.56) (46.11) PSI 70/59 119 113 117 125 147 PSI 75/63 124 120 126 132 155 PSI 80/67 135 129 132 140 162 75 85 95 105 115 (23.89) (29.44) (35) (40.56) (46.
Heating Chart: ℉ (℃) IDT ODT 57/53 47/43 37/33 27/23 17/13 (13.89/11.67) (8.33/6.11) (2.78/0.56) (-2.78/-5) (-8.33/-10.56) BAR 55 30.3 28.5 25.3 22.8 20.8 BAR 65 32.5 30.0 26.6 25.4 23.3 BAR 75 33.8 31.5 27.8 26.3 24.9 ℉ IDT 57/53 47/43 37/33 27/23 17/13 (℃) ODT (13.89/11.67) (8.33/6.11) (2.78/0.56) (-2.78/-5) (-8.33/-10.
10.
11. Disassembly Instructions Note: This part is for reference, the photos may have slight difference with your machine. 11.1 Indoor unit No. Parts name Procedures Remarks 1 Front panel How to remove the front Overview: panel. 1) Pull the below side of the panel and release the clips. Remove the filter and horizontal louver. 2) Clip Clip Remove the fixing screw and open the cover. One screw fixing the cover 3) Lift the panel and release the connector of display ass’y.
2 Electrical How to remove the parts electrical parts. 1) Grounding Coil temp. screws sensor After remove the front panel from procedure 1, pull out the room temp. sensor and evaporator coil sensor. Room temp. sensor Remove the grounding Screw for cover screws. 2) Remove the fixing screw and open the cover of electronic control box. 3) Pull out the connectors of swing motor, fan motor, room temp. sensor and coil temp. sensor. .
3 Evaporator How to remove the evaporator. 1) After remove the front panel ass’y and electrical parts following procedure 1 and procedure 2, remove the pipe holder at the rear side of the unit. Screw of pipe holder 2) Remove the three screws on the evaporator at the base bearing side. 3 screws 3) Remove two screws on the evaporator at the fixed plates and then lift the evaporator ass’y.
4 Fan and How to remove the fan motor and motor. 1) After remove the evaporator ass’y following procedure 1, procedure 2 and procedure 3, remove the four screws fixing the Four screws cover 2) Remove the screw fixing the motor and then pull out the motor.
11.2 Outdoor unit No. 12000 BTU, 230 V, 20 SEER and 9000 / 12000 BTU, 115V, 20 SEER Heat Pumps.
1 Panel plate How to remove the panel plate. 1) Stop operation of the air conditioner and turn “OFF” the power breaker. Screws of top panel 2) Refer to the right side photos, find out the fixing screws of the panels. Screws of front panel Screw of top panel 3) Remove the screws of top panel and remove the top panel. Screws of Screws of big handle front panel on right side plate.
the fixing screws of motor holder and then remove the front panel. Screws of right rear plate 5) Remove the screws of the right side plate and remove the right side plate.
2 Fan ass’y How to remove the fan ass’y. Electronic control box Fan ass’y 1) After remove the panel plate following procedure 1, remove the hex nut fixing the fan and then remove the fan. Reactor Compressor and liquid-gas separator Nut fixing the fan 2) Unfix the hooks and then open the electronic control box cover.
3) Disconnect the connector for fan motor from the electronic control board. Fan motor connector 4) Remove the four fixing screws of the fan motor. 5) Then remove the fan motor. 3 Electrical parts Four screws How to remove the electrical parts. 1) After finish work of item 1 and item 2, remove the three connectors for compressor, crankcase heater and capacitor.
2) Pull out the two black wires connected with the four way valve. Two black wires of four way valve 3) Pull out connectors of the compressor top temp. sensor, condenser coil temp. sensor(T3),outdoor ambient temp. sensor(T4) and discharge temp. sensor(T5). To T3,T4,T5 4) Remove the ground wires . 5) Remove the power supply wires(L1,L2,S). 6) Then remove the electronic control box. 93 To compressor top.
4 Four-way valve How to remove the four-way valve. 1) Perform work of item 1,2,3. 2) Recover refrigerant from the refrigerant circuit. 3) Remove the screw of the coil and then remove the coil. 4) Detach the welded parts of four-way valve and pipe. 5) Then the four-way valve ass’y can be removed The picture of four-way valve may be different from the one on your side. Four-way valve Welded parts Coil of four-way valve, fixing by one screw. 5 Compressor How to remove the compressor.
9000 BTU and 12000 BTU, 230V, 16 SEER No. Part name Procedures 1 Panel plate How to remove the panel plate. 1) Stop operation of the air conditioner and turn “OFF” the power breaker. Remarks Screws of top panel 2) Refer to the right side photos, find out the fixing screws of the panels. Screws of front panel Screw of 3) Remove the screws of top panel and remove the top panel. top panel Screws of Screws of big handle front panel on right side plate.
Screw of the top 4) Remove the screws of the front panel, including the fixing screws of motor holder and then remove the front panel. panel Screws of right rear plate 5) Remove the screws of the right side plate and remove the right side plate.
2 Fan ass’y How to remove the fan ass’y. Electronic control box Fan ass’y 1) After remove the panel plate following procedure 1, remove the hex nut fixing the fan and then remove the fan. Reactor Compressor and liquid-gas separator Nut fixing the fan 2) Unfix the hooks and then open the electronic control box cover.
3) Disconnect the connector for fan motor from the electronic control board. Fan motor connector 4) Remove the four fixing screws of the fan motor. 5) Then remove the fan motor. 3 Electrical parts Four screws How to remove the electrical parts. 1) After finish work of item 1 and item 2, remove the three connectors for compressor, crankcase heater and capacitor.
2) Pull out the two black wires connected with the four way valve. Two black wires of four way valve 3) Pull out connectors of the compressor top temp. sensor, condenser coil temp. sensor(T3),outdoor ambient temp. sensor(T4) and discharge temp. sensor(T5). To T3,T4,T5 4) Remove the ground wires . 5) Remove the power supply wires(L1,L2,S). 6) Then remove the electronic control box. 99 To compressor top.
4 Four-way valve How to remove the four-way valve. 1) Perform work of item 1,2,3. 2) Recover refrigerant from the refrigerant circuit. 3) Remove the screw of the coil and then remove the coil. 4) Detach the welded parts of four-way valve and pipe. 5) Then the four-way valve ass’y can be removed The picture of four-way valve may be different from the one on your side. Four-way valve Welded parts Coil of four-way valve, fixing by one screw. 5 Compressor How to remove the compressor.
No. 18000 BTU, Both 16 and 20 SEER Models. Part name Procedures Panel plate How to remove the panel Remarks plate. 1) Screws of top panel Stop operation of the air conditioner and turn “OFF” the power breaker. 2) Refer to the right side photos, find out the fixing Screws of front panel screws of the panels. Screw of top panel 3) Screws of Remove the screws of big handle top panel and remove the on right side plate. top panel.
4) Remove the screws of Screw of the top the front panel, including panel the fixing screws of motor holder and then remove the front panel. Screws of right rear plate Screw of top panel 5) Remove the screws of the right side plate and remove the right side plate.
2 Fan ass’y How to remove the fan Fan Electronic control box ass’y. 1) After remove the panel plate following procedure 1, remove the hex nut fixing the fan and then remove the fan. Two reactors Compressor and liquid-gas separator Nut fixing the fan 2) Remove the one fixing screw. Unfix the hooks and then open the electronic control box cover.
3) Release the fan motor Fan motor connector connector and four way valve connector. Four way valve connector 4) Remove the four fixing screws of the fan motor. 5) Then remove the fan Four screws motor. 3 Electrical parts How to remove the electrical parts. 1) After finish work of item 1 and item 2, remove the two connectors for the compressor and the compressor crankcase heater.
2) Release the three temp. sensor connectors. 3) Remove the connector of reactor. 4) Remove the connector of electronic expansion valve. 5) Remove the grounding screw. 6) Remove the power supply wires(L1,L2,S). 7) Then remove the electronic control box.
4 Four-way valve How to remove the four-way valve. 1) The picture of four-way valve may be different from the one on your side. Perform work of Four-way item1,2,3. 2) valve Recover refrigerant Welded from the refrigerant circuit. 3) parts Remove the screw of the coil and then remove the coil. 4) Detach the welded parts of four-way valve and pipe. 5) Then the four-way valve ass’y can be removed Coil of four-way valve, fixing by one screw. 5 Compressor How to remove the compressor.
No. 18000 BTU, 16 SEER Part name Procedures Panel plate How to remove the panel Remarks plate. 1) Screws of top panel Stop operation of the air conditioner and turn “OFF” the power breaker. 2) Refer to the right side photos, find out the fixing Screws of front panel screws of the panels. Screw of top panel 3) Screws of Remove the screws of big handle top panel and remove the on right side plate. top panel.
4) Remove the screws of Screw of the top the front panel, including panel the fixing screws of motor holder and then remove the front panel. Screws of right rear plate Screw of top panel 5) Remove the screws of the right side plate and remove the right side plate.
2 Fan ass’y How to remove the fan Fan Electronic control box ass’y. 1) After remove the panel plate following procedure 1, remove the hex nut fixing the fan and then remove the fan. Two reactors Compressor and liquid-gas separator Nut fixing the fan 2) Remove the one fixing screw. Unfix the hooks and then open the electronic control box cover.
Fan motor connector 3) Release the fan motor Four way valve connector connector and four way valve connector. 4) Remove the four fixing screws of the fan Four screws motor. 5) Then remove the fan motor. 3 Electrical parts How to remove the electrical parts. 1) After finish work of item 1 and item 2, remove the two connectors for the compressor and the compressor crankcase heater.
2) Release the three temp. sensor connectors. 3) Remove the connector of reactor. 4) Remove the connector of electronic expansion valve. 5) Remove the grounding screw. 6) Remove the power supply wires(L1,L2,S). 7) Then remove the electronic control box.
4 Four-way valve How to remove the four-way valve. 1) The picture of four-way valve may be different from the one on your side. Perform work of Four-way item1,2,3. 2) valve Recover refrigerant Welded from the refrigerant circuit. 3) parts Remove the screw of the coil and then remove the coil. 4) Detach the welded parts of four-way valve and pipe. 5) Then the four-way valve ass’y can be removed Coil of four-way valve, fixing by one screw. 5 Compressor How to remove the compressor.
No. 24000 BTU, 16 and 20 SEER Models. Part name Procedures Panel plate How to remove the panel plate. 1) Stop operation of the air conditioner and turn “OFF” the power breaker. Remarks Screws of top panel 2) Refer to the right side photos, find out the fixing screws of the panels. Screws of front panel Screws of the right side panel 3) Remove the screws of top panel and remove the top panel. Screws of big handle on right side plate.
4) Remove the screws of the front panel, including the fixing screws of motor holder and then remove the front panel. Screws of right rear plate 5) Remove the screws of the right side plate and remove the right side plate.
2 Fan ass’y How to remove the fan ass’y. Fan LAK board(optional) Electronic control box 1) After remove the panel plate following procedure 1, remove the hex nut fixing the fan and then remove the fan. Accumulator Three reactors Compressor and liquid-gas separator Nut fixing the fan 2) Unfix the hooks and then open the electronic control box cover.
3) Disconnect the connector for fan motor from the electronic control board. Fan motor connector 4) Remove the four fixing screws of the fan motor. 5) Then remove the fan motor. 3 Electrical parts Four screws How to remove the electrical parts. 1) After finish work of item 1 and item 2, remove the three connectors for the compressor and the reactors and the compressor crankcase heater. Two blue wires of four way valve 2) Pull out the two blue wires connected with the four way valve.
3) Pull out connectors of the compressor top temp. sensor, condenser coil temp. sensor(T3),outdoor ambient temp. sensor(T4) and discharge temp. sensor(T5). Four temp. sensor connectors 4) Remove the grounding screw. Grounding screw 5) Remove the power supply wires(L1,L2,S). 6) Then remove the electronic control box.
4 Four-way valve How to remove the four-way valve. 1) Perform work of item1,2,3. 2) Recover refrigerant from the refrigerant circuit. 3) Remove the screw of the coil and then remove the coil. 4) Detach the welded parts of four-way valve and pipe. 5) Then the four-way valve ass’y can be removed The picture of four-way valve may be different from the one on your side. Four-way valve Welded parts Coil of four-way valve, fixing by one screw 5 Compressor How to remove the compressor.