Description
The A+CLASS™ Daylight Sensor provides daylight level information to the Classroom Control Module. The Daylight Sensor continuously
measures daylight levels and sends this information to the Classroom Control Module.
speciFicAtions
• Supply voltage (supplied by Classroom Control Module): 24VDC
• UL and cUL listed when installed as part of a complete A+Class™ System
• 5-year warranty when installed as part of a complete A+Class™ System
precAUtions
CAUTION: FOR USE WITH CLASS 2, LOW VOLTAGE SYSTEMS ONLY. DO NOT USE IN HIGH VOLTAGE APPLICATIONS.
• Read and understand all instructions before beginning installation.
• NOTICE: For installation by a licensed electrician in accordance with National and/or local Electrical Codes.
• NOTICE: For indoor use only.
CAUTION: USE COPPER CONDUCTOR ONLY.
• Conrm device ratings are suitable for application prior to installation. Use of device in applications beyond its specied ratings or in
applications other than its intended use may cause an unsafe condition and will void manufacturer’s warranty.
• NOTICE: Do not install if any damage to product is noticed.
incLUDeD coMponents
1. Classroom Control Module (CCM)
2. 50' Green low voltage cable
with CAT5 connection on one end and snap-in connection which mates to Daylight Sensor on the other end (See Figures 1 and 1a).
3. Daylight Sensor with pre-installed low voltage Quick–To-Install™ (QTI) connector. The sensor’s QTI connector quickly mates to the
snap-in QTI connection on Green low voltage cable, also provided (See Figure 2).
4. A+CLASS™ Lighting xtures with 0-10V dimming ballasts installed for the General lighting mode.
DAYLiGHt sensor pLAceMent
The Daylight Sensor must be placed to see only daylight with no contribution from articial light sources. The sensor typically mounts on the
ceiling between the window and the row of xtures closest to the window. For skylight applications, the sensor mounts in the lightwell. The
sensor is aimed toward the daylight. A light meter is required for light level measurements at the task areas (See Figure 3).