Network Communications—N2 Communications Bus
If you need to place the 2110 modem between two segments of N2 Bus,
wire a stub length of six inches or less as shown in Figure 17 and
terminate the two pairs of N2 Bus cable at the end of the stub length.
To N CM
To N 2
Devices
N2 Bus
Fiber
Cable
STUBCONN
To N2 Devices
Use wire nuts to
join N2 cable to 
stub length.
N2 +
N2 -
REF
Maximum stub 
length is six inches.
S.I.Tech
2110
RT
S.I.Tech
2110
RT
S.I.Tech
2110
RT
Figure 17: Connecting 2110 Modem in Between
Two N2 Bus Segments
Fiber Modem
Between
Two Segments