Instruction manual

Installation and Operation
8 CC/CCS Power Conditioner User Manual
in doubt regarding wire sizing, consult the
U.S. National Electrical Code, Table
310-16, or your local electrical codes.
Fig. 2: CC and CCS Hardwire Connections
6. Connect the input phase wires to the input
terminal block. Separate the input power
cable to the ONEAC power conditioner
from the equipment power cable. Data
cables should be kept as far away from any
power cables as possible. Torque all
connections. Refer to the torque
s p e c i f i c a t i o n s i n M a i n t e n a n c e o n p a g e 1 9 .
7. Replace the unit or rear terminal cover.
8. Follow the procedure in the section
Verifying Your Installation on page 4.
Output Connections The output connections are supplied as various
NEMA style receptacles. Some models are
available with a hardwire output connection.
Hardwire models have a 1/2” (13 mm) conduit
connection with internal terminal blocks
enclosed within an attached wiring box. An
additional hardwire version is available that
utilizes a flat conduit landing plate attached to
the rear of the unit that will accept 1/2 or 3/4
inch conduit.
Your ONEAC cord-connected, CC and CCS
Series, power conditioners will meet your
power conditioning requirements without the
CCxx48 Series
All Other CC and CCS Series - Hardwire