Technical data

48 • Fieldbus coupler/controller
Fieldbus coupler 750-310
WAGO-I/O-SYSTEM 750
CC-Link
System area flag Description
Reset on T-Bus-Error flag
Reaction on F-Bus-Error flags (2 bits)
Reaction on T-Bus-Error flags (2 bits)
Initial data processing request flag/complete flag Used when the remote device requests the initial proces-
sing to the user's sequence after the power of the remote
device is turned on or after a hardware reset.
Initial data setup complete flag/request flag Used when the user's sequence requests the initial setup to
the remote device.
Error status flag Used when the remote device notifies an error other than
watchdog timer errors.
Remote station ready flag Used to notify the completion of the initial processing for
the initial data setup.
3.1.4.2.3 Remote Register Area
The entire areas of the remote registers for the remote device station are user-
defined areas.
Link register Signal name Link register Signal name
User defined area User defined area
RWrm0 RWwm0
RWrm1 RWwm1
RWrm2 RWwm2
RWrm3
One station: 4 points
RWwm3
One station: 4 points
RWrm4 RWwm4
RWrm5 RWwm5
RWrm6 RWwm6
RWrm7
Two stations: 8 points
RWwm7
Two stations: 8 points
RWrm8 RWwm8
RWrm9 RWwm9
RWrm10 RWwm10
RWrm11
Three stations: 12 points
RWwm11
Three stations: 12 points
RWrm12 RWwm12
RWrm13 RWwm13
RWrm14 RWwm14
RWrm15
Four stations: 16 points
RWwm15
Four stations: 16 points
Note
A process image restructuring may result if a node is changed or extended. In
this case the process data addresses also change in comparison with earlier
ones. In the event of adding a module, take the process data of all previous
modules into account.