Specifications
EVALPFC-3kW-IPZ65R019C7
19
Application Note AN 2014-06
V1.1 January 2015
10 Test report
All test condition are based on 60°C heat sink temperature.
For the efficiency test it is important to take the voltage sensing on the input and output power with the
Vin_sense and Vout_sense right beside the power connections.
10.1 Load and Line Test
Input
V
IN
I
IN
P
IN
U
OUT
I
OUT
P
OUT
Eff.
PF
85Vac
84.87
1.5715
131.26
400.89
0.3001
120.21
91.58159
0.9842
84.8
3.0311
255.33
400.9
0.5996
240.27
94.10175
0.9934
84.73
4.5068
380.53
400.86
0.9002
360.71
94.79148
0.9965
84.66
5.991
506.1
400.89
1.2004
481.1
95.06027
0.9978
84.58
7.486
632.1
400.89
1.4992
600.8
95.04825
0.9983
84.51
8.997
759.4
400.87
1.7993
721
94.94338
0.9988
84.44
10.522
887.6
400.87
2.1001
841.6
94.81749
0.999
84.37
12.063
1016.8
400.89
2.399
961.4
94.55153
0.9991
84.29
13.621
1147.2
400.88
2.6993
1081.8
94.29916
0.9991
84.21
15.191
1278.3
400.89
2.9969
1201.1
93.96073
0.9992
230Vac
229.65
1.3798
310.35
400.89
0.7479
299.78
96.59417
0.9794
229.72
2.6986
615.7
400.89
1.4978
600.4
97.51502
0.9931
229.66
4.0199
919.8
400.89
2.2452
900
97.84736
0.9963
229.6
5.3548
1226.3
400.88
2.9956
1200.8
97.92057
0.9975
229.54
6.692
1533.3
400.85
3.7472
1501.9
97.95213
0.9982
229.47
8.027
1839.4
400.87
4.4934
1801
97.91236
0.9986
229.41
9.373
2147.7
400.88
5.2446
2102.1
97.8768
0.9988
229.34
10.725
2456.8
400.87
5.993
2402.1
97.77353
0.9988
229.28
12.076
2765.9
400.82
6.74
2701.1
97.65718
0.999
229.21
13.437
3076.9
400.88
7.489
3001.6
97.55273
0.999
Out of the table one can see, that the full load efficiency is improved by only changing from 3pin to 4pin
configuration. Due to this advantage it can be possible to replace a current 3pin PFC stage with a MOSFET
of one step higher R
DS(on)
.
This will help to increase the efficiency all over the power range beside full load at
low line. Therefore it will help to enter into the TITANUM Standard for server SMPS.