ArmorPoint I/O
AAnnaalloogg,, TThheerrmmooccoouuppllee,,
aanndd RRTTDD II//OO MMoodduulleess
Choose analog, thermocouple, and/or RTD I/O modules when you need:
The ArmorPoint analog and temperature I/O modules support: on-board, channel-level data
alarming (four set-points per channel); scaling to engineering units; channel-level
diagnostics (electronic bits and LEDs); and integer format.
y Individually configurable channels to use the module(s) with a variety of sensors.
y On-board scaling to eliminate the need to scale the data in the controller. Controller
processing time and power are preserved for more important tasks, such as I/O control,
communications, or other user-driven functions.
y On-line configuration. Modules can be configured in the RUN mode using the
programming software or the control program. This allows you to change configuration
while the system is operating. For example, the input filter for a particular channel could
be changed, or a channel could be disabled based on a batch condition.
To use this
feature, the controller and network interface must also support this feature.
y Over- and under-range detections and indications. This eliminates the need to test
values in the control program, saving valuable processing power of the controller. In
addition, since alarms are handled by the module, the response is faster and only a
single bit per channel is monitored to determine if an error condition has occurred.
y Ability to direct output device operation during an abnormal condition. Each
channel of the output module can be individually configured to hold its last value or
assume a user-defined value on a fault condition. This feature allows you to set the
condition of your analog devices, and therefore your control process, which may help to
ensure a reliable shutdown.
y Ability to individually enable and disable channels. Disabling unused channels
improves module performance.
y Selectable input filters This lets you select the filter frequencies for each channel
that best meets the performance needs of your application based on environmental
limitations. Lower filter settings provide greater noise rejection and resolution. Higher
filter settings provide faster performance.
Note: The analog modules provide four input
filter selections; RTD and thermocouple modules provide six.
y Selectable response to broken input sensor. This feature provides feedback to the
controller that a field device is not connected or operating properly. This lets you specify
corrective action based on the bit or channel condition.
y High accuracy. The modules share a high accuracy rating of ±0.1% of full-scale
accuracy at 25 °C.