User manual

27
Publication 1738-SG001B-EN-P
ArmorPoint I/O
PPoowweerr DDiissttrriibbuuttiioonn GGeenneerraall SSppeecciiffiiccaattiioonnss
11773388--FFPPDD 11773388--EEPP2244DDCC
Power Supply Requirements
Note: In order to comply with CE Low Voltage
Directives (LVD), you must use a Safety Extra Low
Voltage (SELV) or a Protected Extra Low Voltage
(PELV) power supply to power this adapter
Field Side Power Requirements, Max. 24V dc (+20% = 28.8V dc max.) @ 400 mA 24V dc (+20% = 28.8V dc max.) @ 400 mA
Inrush Current, Max.
6 A for 10 ms
Overvoltage Protection, Inputs Reverse polarity protected Reverse polarity protected
Power Supply Interruption Protection
Output voltage will stay within specifications when input drops out
for 10 ms at 10V with max load
Power Supply Input Voltage, Nom.
12V/24V dc
120V/220V ac
24V dc
Operating Voltage Range
10…28.8V dc
120V/240V ac
10…28.8V dc
Power Consumption, Max.
9.8 W @ 28.8V dc
Power Dissipation, Max. 3.0 W @ 28.8V dc
Thermal Dissipation, Max. 10.0 BTU/hr @ 28.8V dc
Isolation Voltage 1528V rms 1250V rms
Field Power Bus Supply Voltage, Nom.
12V dc, 24V dc, (10…28.8V dc range)
120V ac, 240V ac 50/60 Hz
12V dc or 24V dc
Field Power Bus Supply Current, Max. 10 A 10 A