118 Status Indicators
MEM 
SAVE
Off The user program and configuration 
data are not actively being saved to 
flash memory.
Normal Operation - No action is required.
Green The user program and configuration 
data are being saved to flash memory.
I/O Off • There are no devices in the I/O 
configuration of the controller.
• The controller does not contain a 
project (controller memory is 
empty).
Steady 
green
The controller is communicating with 
all of the devices in its I/O 
configuration.
I/O Flashing 
green
One or more devices in the controller’s 
I/O configuration are not responding.
To determine why a device may not be responding, perform this 
procedure.
1. Verify that all I/O modules in your project are installed in the 
same order.
2. Verify that all devices have been updated to the latest major 
and minor firmware revisions.
3. Use RSLogix 5000 programming software Online help to 
determine which I/O module is not responding.
Flashing red The controller is not communicating 
with any of the devices in its I/O 
configuration.
OK Off • No power is applied.
• If MEM SAVE is green, the user 
program and configuration data are 
being saved to flash memory.
Normal Operation - No action is required.
Flashing red The controller requires a firmware 
update.
1. Download the latest firmware from 
http://support.rockwellautomation.com
.
2. To install the latest firmware, either
• use the ControlFlash utility.
• use AutoFlash.
• use your CompactFlash card.
For additional information, see the CompactLogix Controllers 
Installation Guide, publication 1768-IN004
.
A major recoverable fault occurred on 
the controller.
To clear the fault, perform this procedure.
1. Turn the controller keyswitch from PROG to RUN to PROG.
2. Go online with RSLogix 5000 programming software.
CompactLogix Controller Status Indicators
Indicator Condition Interpretation Recommended Actions