User manual
15 Publication 1734-UM015A-EN-E - November 2009
Chapter
 2
Install POINT I/O DeviceLogix Modules
If you are using ArmorPOINT I/O modules 
(1738-8CFGDLXM8/M12/M23), go to Chapter 3, 
Install ArmorPOINT I/O 
DeviceLogix Modules.
About This Chapter
Read this chapter for installation and wiring information including how to 
complete the following: 
• Install the Mounting Base Assembly
• Install an I/O Module
• Install the Removable Terminal Block
• Remove a 1734-TB or 1734-TBS Base
• Wire the Modules
ATTENTION
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 
industrial environment, in overvoltage Category II applications 
(as defined in IEC publication 60664-1), at altitudes up to 2000 m 
(6561 ft) without derating.
This equipment is considered Group 1, Class A industrial 
equipment according to IEC/CISPR 11. Without appropriate 
precautions, there may be potential difficulties ensuring 
electromagnetic compatibility in other environments due to 
conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be 
mounted within an enclosure that is suitably designed for those 
specific environmental conditions that will be present and 
appropriately designed to prevent personal injury resulting from 
accessibility to live parts. The interior of the enclosure must be 
accessible only by the use of a tool. Subsequent sections of this 
publication may contain additional information regarding specific 
enclosure type ratings that are required to comply with certain 
product safety certifications.
See NEMA Standards 250 and IEC 60529, as applicable, for 
explanations of the degrees of protection provided by different 
types of enclosure. Also, see the appropriate sections in this 
publication, as well as the Allen-Bradley publication 1770-4.1 
(Industrial Automation Wiring and Grounding Guidelines), for 
additional installation requirements pertaining to this equipment.