User manual
27 Publication 1734-UM015A-EN-E - November 2009
Chapter
 3
Install ArmorPOINT I/O DeviceLogix Modules
If you are using POINT I/O modules (1734-8CFGDLX), go to Chapter 2, 
Install POINT I/O DeviceLogix Modules.
About This Chapter
Read this chapter for information about how to install ArmorPOINT I/O 
modules to include the following: 
• Install the Mounting Base
• Install the Module
• Wire the Modules
• Remove the Modules
Install the Mounting Base
Mount the I/O base on a wall or panel, using the screw holes provided in the 
base.    
ATTENTION
This equipment is considered Group 1, Class A industrial 
equipment according to IEC/CISPR Publication 11. Without 
appropriate precautions, there may be potential difficulties 
ensuring electromagnetic compatibility in other environments 
due to conducted as well as radiated disturbance.
IMPORTANT
The ArmorPOINT I/O module must be mounted on a grounded 
metal mounting plate or other conductive surface.
ATTENTION
Make sure all connectors and caps are securely tightened to 
properly seal the connections against leaks and maintain IP 
enclosure type requirements.
ATTENTION
To comply with the CE Low Voltage Directive (LVD), all 
connected I/O must be powered from a source compliant with 
the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage 
(PELV).