User manual
Publication 1734-UM015A-EN-E - November 2009
DeviceLogix for POINT I/O and ArmorPOINT I/O on Ethernet/ControlNet 47
Launch RSNetworx for 
DeviceNet to Configure the 
Module
The Point I/O DeviceLogix module can only be configured using RSNetWorx 
for DeviceNet.
The following example assumes that the module is configured while it is 
online. If the module is configured offline, then apply the same procedure 
when you download the contents of the DNT file to the I/O module.
To configure the module:
1. Start RSNetworx for DeviceNet.
2. Go online by doing one of the following:
• Click the Online button.
• On the Network menu, click Online.
• Press <F10>.
The RSLinx Browse window appears.
3. Navigate the tree down to the EtherNet/IP or ControlNet Point I/O or 
ArmorPOINT I/O adapter.
4. Expand the tree branch for the adapter.
You should see two additional ports. The first is the backplane, and the 
second is a DeviceNet port. Physically they are the same port, which is 
the backplane.
RSNetWorx needs a DeviceNet port. 