DeviceLogix Capabilities  79
Enable/Disable Logic
For logic to execute, it must be enabled. While editing online with RSNetWorx 
for DeviceNet, you can enable logic.
Logic Enable On
Use the Logic Enable On function to notify the device to start processing the 
stored logic diagram. To set Logic Enable On, select Communications > Logic 
Enable On.
Logic Enable Off
Use the Logic Enable Off option to notify the device to stop executing the 
logic program. When you select this option, the device enters an idle state, 
turning off the Logic Enable Bit in the produced data. The Logic Enable bit in 
the Produced I/O assembly of the device reflects a 0 or 1 for Logic Enable 
Off or Logic Enable On. To set Logic Enable Off, select Communications > 
Logic Enable Off.
Dependent Mode
Logic will also be enabled or disabled if the Dependent Mode parameter is 
Enabled. In this case, logic will execute following the state of the owning 
connection. When the connection is in RUN, the logic is enabled. When the 
connection is in Idle, Fault, or non-existent, logic is disabled.
You can also enable or disable logic through explicit messages from the 
owning controller. See Messaging
.