Publication 1734-UM015A-EN-E - November 2009
Troubleshooting 85
Network Status
DeviceLogix Status
I/O Status
Indication Probable Cause Recommended Action
Off Device is not online.
- Device has not completed 
dup_MAC_id test.
- Device not powered - check module 
status indicator.
Apply power to device, wait for 
dup_MAC_id to complete, and 
correct, as needed.
Green Device is online and has connections 
in the established state.
None.
Flashing 
green
Device is online but has no 
connections in the established state.
None .
Flashing red One or more I/O connections are in 
the timed-out state.
This could also mean a peer is not 
producing data at all, or it is not 
configured correctly.
Check I/O connection with 
master. Verify peers are present 
and configured properly.
Red Critical link failure - failed 
communication device. Device 
detected error that prevents it 
communicating on the network.
Verify that adapter and terminal 
bases are properly installed, and 
reinstall, as needed.
Flashing 
red/green
Device is in self-test. None.
Indication Probable Cause Recommended Action
Off DeviceLogix program is not 
controlling outputs.
None.
Green DeviceLogix program is controlling 
outputs.
None.
Flashing 
green
At least one input in DeviceLogix 
program is forced on/off.
None.
Indication Probable Cause Recommended Action
Off Input or output is in the OFF state. None.
Yellow Input or output is in the ON state. None.