Installation manual

8-2 Frame 11 Installation
Figure 8.2 Enclosure Code B (NEMA/UL Type 1, IP21) and K (NEMA/UL Type 1, IP21
w/Conformal Coat)
Operating Temperatures
Frame 11 drives require a minimum of 3900 m
3
/h (2295 cfm) of cooling air.
200 mm
(7.87 in.) Min.
838 mm
(33.0 in.) Min.
PowerFlex Drive Voltage Class Amp Rating
Surrounding Air Temperature
Normal Duty Heavy Duty
700H All All 0 to 40° C
(32 to 104° F)
0 to 40° C
(32 to 104° F)
700S 400/480V AC
(540/650V DC)
All 0 to 40° C
(32 to 104° F)
0 to 40° C
(32 to 104° F)
600/690V AC
(810/932V DC)
460, 502 0 to 40° C
(32 to 104° F)
0 to 40° C
(32 to 104° F)
600/690V AC
(810/932V DC)
590 0 to 35° C
(32 to 95° F)
0 to 35° C
(32 to 95° F)