Installation manual

9-16 Frame 12 Installation
Output Power Wiring
Frame 12 drives utilize two parallel power structures, and therefore have
two sets of output power terminals. You must connect the motor to both sets
of output power terminals.
Important:Parallel wiring must have the same cable dimensions, type and
routing. Non-symmetrical wiring may cause unequal loading
between the converters and reduce the drive’s ability to deliver
current to the motor.
Important:The minimum cable length for parallel motor cables from the
drive to the point where the cables connect is 5m (16.4 ft). Join
the parallel cables at the motor end (not the drive end). Or,
install a reactor on the output of each power module with a
minimum of 5 µH prior to joining the parallel cables at the
motor end.
Figure 9.7 Frame 12 Motor Wiring Example
1T1 1T2 1T3 2T1 2T2 2T3PE PE
Motor Frame
Motor
5 m
minimum