Installation manual

10-2 Frame 13 Installation
Minimum Mounting
Clearances
Operating Temperatures
Frame 13 drives require a minimum of 4200 m
3
/h (2472 cfm) of cooling air
for the Inverter unit and 1150 m
3
/h (677 cfm) of cooling air for each
Converter unit.
800 mm
(31.50 in.) Min.
200 mm
(8.0 in.) Min.
1600 mm, Style “A” Enclosure Shown.
PowerFlex
Drive Voltage Class Amp Rating
Surrounding Air Temperature
Normal Duty Heavy Duty
700H All All 0 to 40° C (32 to 104° F) 0 to 40° C (32 to 104° F)
700S 400/480V AC
(540/650V DC)
All 0 to 40° C (32 to 104° F) 0 to 40° C (32 to 104° F)
600/690V AC
(810/932V DC)
920, 1030 0 to 40° C (32 to 104° F) 0 to 40° C (32 to 104° F)
600/690V AC
(810/932V DC)
1180 0 to 35° C (32 to 95° F) 0 to 35° C (32 to 95° F)