Installation manual

Appendix A
Specifications
Category PowerFlex 700H PowerFlex 700S
Agency
Certification
Listed to UL508C and CAN/CSA-C2.2 No. 14-M91. UL and cUL Listed to UL508C and CAN/CSA - 22.2 No. 14-95.
Marked for all applicable European Directives
(1)
EMC Directive (89/336/EEC)
EN 61800-3 Adjustable Speed electrical power drive systems
Low Voltage Directive (73/23/EEC)
EN 50178 Electronic Equipment for use in Power Installations
Marked for all applicable European Directives
EMC Directive (89/336/EEC)
Emissions:
EN 61800-3 Adjustable Speed electrical power drive systems Part 3
Low Voltage Directive (73/23/EEC)
EN 50178 Electronic Equipment for use in Power Installations
Certified to AS/NZS, 1997 Group 1, Class A. Certified to AS/NZS, 1997 Group 1, Class A.
Certified to ATEX directive 94/9/EC. Group II Category (2) GD
Applications with ATEX Approved Motors. Refer to Appendix E -
Instructions for ATEX Approved PowerFlex 700H Drives in Group II
Category (2) Applications with ATEX Approved Motors for more
information.
Certified to ATEX directive 94/9/EC. Group II Category (2) GD Applications
with ATEX Approved Motors. PowerFlex 700S Phase II Control drives only.
Refer to publication 20D-UM006… for more information.
NA TUV functional safety report only (no FS mark on the label)
The drive is also designed to meet the following specifications:
NFPA 70 - US National Electrical Code
NEMA ICS 7.1 - Safety standards for Construction and Guide for
Selection, Installation and Operation of Adjustable Speed Drive
Systems.
IEC 146 - International Electrical Code.
The drive is designed to meet applicable requirements of the following
codes/standards:
IEC 61800-2 Adjustable speed electrical power drive systems - General
requirements
IEC 61800-5-1 Adjustable speed electrical power drive systems - Safety
requirements
NFPA 70 - US National Electrical Code
(1)
Applied noise impulses may be counted in addition to the standard pulse train causing erroneously high [Pulse Freq] readings.
N223
II 2 G/D
TUV
Rheinland
Product Safety
.
.
Production inspected
W
E
C
TUV
Rheinland
.
.
Functional
Safety
Bauart geprüft
Type approved
EN 50178
Category Specification PowerFlex 700H PowerFlex 700S
Protection Drive
380/400V 480V 500V 600V 690V 380/400V 480V 500V 600V 690V
AC Input Overvoltage Trip: 611Vac 611Vac 611Vac 806Vac 806Vac 675Vac 675Vac 675Vac 889Vac 889Vac
AC Input Undervoltage Trip: 235Vac 235Vac 235Vac 326Vac 326Vac Adjustable
Bus Overvoltage Trip: 911Vdc 911Vdc 911V dc 1200V dc 1200V dc 911Vdc 911Vdc 911Vdc 1200Vdc 1200Vdc
Bus Undervoltage Shutoff/Fault: 333Vdc 333Vdc 333Vdc 461Vdc 461Vdc Adjustable
Nominal Bus Voltage (Full Load): 517Vdc 621Vdc 645Vdc 776Vdc 890Vdc 540Vdc 648Vdc 645Vdc 810Vdc 931V dc
Heat Sink Thermistor: Monitored by microprocessor overtemp trip Monitored by microprocessor overtemp trip
Drive Overcurrent Trip
Software Overcurrent Trip:
Hardware Overcurrent Trip:
Instantaneous Current Limit:
360% of rated Heavy Duty current (typical)
Calculated value, 105% of motor rated to 200% of drive rated
360% of rated Heavy Duty current (typical)
Line transients: up to 6000 volts peak per IEEE C62.41-1991 Up to 6000 volts peak per IEEE C62.41-1991
Control Logic Noise Immunity: Showering arc transients up to 1500V peak Showering arc transients up to 1500V peak
Power Ride-Thru: 15 milliseconds at full load 15 milliseconds at full load
Logic Control Ride-Thru: 0.5 seconds minimum, 2 seconds typical 0.25 seconds, drive not running
Ground Fault Trip: Phase-to-ground on drive output Phase-to-ground on drive output
Short Circuit Trip: Phase-to-phase on drive output Phase-to-phase on drive output