Installation manual

A-2 Specifications
Environment Altitude: 1000 m (3300 ft.) maximum without derating. Derate the drive
by 1% for every 100 m (328 ft.) above 1000 m (3300 ft.).
1000 m (3300 ft.) maximum without derating. Derate the drive
by 1% for every 100 m (328 ft.) above 1000 m (3300 ft.).
Maximum Surrounding Air Temperature
without De-rating:
Based on drive rating, refer to Drive Frame chapters Based on drive rating, refer to Drive Frame chapters.
Storage Temperature (all const.): –40 to 60° C (–40 to 140° F) –40 to 70° C (–40 to 158° F)
Atmosphere: Important: Drive must
not be installed in an area where the
ambient atmosphere contains volatile or corrosive gas, vapors
or dust. If the drive is not going to be installed for a period of
time, it must be stored in an area where it will not be exposed to
a corrosive atmosphere.
Important: Drive must
not be installed in an area where the
ambient atmosphere contains volatile or corrosive gas, vapors
or dust. If the drive is not going to be installed for a period of
time, it must be stored in an area where it will not be exposed to
a corrosive atmosphere.
Relative Humidity: 5 to 95% non-condensing 5 to 95% non-condensing
Shock:
Non-operational 15G peak for 11ms duration (±1.0 ms) 15G peak for 11ms duration (±1.0 ms)
Vibration: 2 mm (0.0787 in.) displacement, 1G peak
EN50178 / EN60068-2-6
2 mm (0.0787 in.) displacement, 1G peak
EN50178 / EN60068-2-6
Sound: Frame Sound
Level
Back-
ground
Noise
Level
Note: Sound pressure
level is measured at 1
meter. All devices
measured are 400V
IP21 and in power up
mode.
Frame Sound
Level
Back-
ground
Noise
Level
Note: Sound pressure
level is measured at 1
meter. All devices
measured are 400V
IP21 and in power up
mode.
9 78 dba 49 dba 9 78 dba 49 dba
10 77 dba 49 dba 10 77 dba 49 dba
13 76d ba 46 dba 13 76d ba 46 dba
Electrical AC Input Voltage Tolerance: ±10% ±10%
Frequency Tolerance: 47-63 Hz. 47-63 Hz.
Input Phases: Three-phase input provides full rating for all drives.
Single-phase operation provides 50% of rated current.
Three-phase input provides full rating for all drives.
Single-phase operation provides 50% of rated current.
Displacement Power Factor: 0.98 across entire speed range. 0.98 across entire speed range.
Efficiency: 97.5% at rated amps, nominal line volts. 97.5% at rated amps, nominal line volts.
Maximum Short Circuit Rating: 200,000 Amps symmetrical. 200,000 Amps symmetrical.
Actual Short Circuit Rating: Determined by AIC rating of installed fuse/circuit breaker. Determined by AIC rating of installed fuse/circuit breaker.
Maximum Drive to Motor Power Ratio: Recommended not greater than 2:1 ratio. Drive to motor rating cannot exceed a 2:1 ratio.
Category Specification PowerFlex 700H PowerFlex 700S