Installation manual

A-12 Specifications
Table A.H 932 Volt DC Input Frames 9 - 14 Drive Ratings
Drive Catalog
Number
Frame
kW Rating
PWM
Freq. Temp.
DC Input
Ratings Output Amps
ND HD kHz ° C Amps Cont. 1 Min. 3 Sec.
20xM170 9 160 2 40 200 170 187 245
132 2 40 170 144 216 245
20xM208 9 200 2 35 245 208 230 289
160 2 40 200 170 250 289
20xM261 10 250 2 40 307 261 287 375
200 2 40 245 208 312 375
20xM325 10 315 2 40 383 325 358 470
250 2 40 307 261 392 470
20xM385 10 355 2 40 453 385 424 585
315 2 40 383 325 488 585
20xM416 10 400 2 35 490 416 458 585
315 2 40 383 325 488 585
20xM460 11 450 2 40 542 460 506 693
355 2 40 453 385 578 693
20xM502 11 500 2 40 591 502 552 828
400 2 40 542 460 690 828
20xM590 11 560 2 35 695 590 649 885
500 2 35 591 502 753 904
20xM650 12 630 2 40 765 650 715 1062
560 2 40 695 590 885 1062
20xM750 12 710 2 40 883 750 825 1170
630 2 40 765 650 975 1170
20xM820
(1)
(1)
20DM820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz.
12 800 2 35 965 820 902 1170
630 2 35 765 650 975 1170
20xM920 13 900 2 40 1038 920 1012 1380
800 2 40 925 820 1230 1410
20xM1K0 13 1000 2 40 1162 1030 1133 1545
900 2 40 1038 920 1380 1755
20xM1K1 13 1100 2 35 1331 1180 1298 1755
1000 2 35 1162 1030 1463 1755
20xM1K5 14 1500 2 40 1766 1500 1650 2250
1300 2 40 1530 1300 1950 2340
20xM1K9
(2)
(2)
Not available with 700S Control.
14 1800 2 40 2237 1900 2090 2700
1500 2 40 1766 1500 2250 2700
20xM2K2
(2)
14 2000 2 30 2649 2250 2475 3335
1800 2 30 2237 1900 2782 3335