Installation manual

Specifications A-17
Table A.L 690 Volt AC Input Frames 9 - 14 Drive Protection Devices
20xE1K0 13 1100 994 1300 (1 per phs)
650 (2 per phs)
2300 1300 (1 per phs)
650 (2 per phs)
3000 170M6466
(5)
3000 1300
1000 888 1200
(1 per phs)
600 (2 per phs)
2000 1200 (1 per phs)
600 (2 per phs)
2700 170M6466
(5)
2700 1200
20xE1K1 13 1300 1139 1500 (1 per phs)
750 (2 per phs)
2600 1500 (1 per phs)
750 (2 per phs)
3500 170M6466
(5)
3500 1500
1100 994 1300 (1 per phs)
650 (2 per phs)
2200 1300 (1 per phs)
650 (2 per phs)
3000 170M6466
(5)
3000 1300
20xE1K5 14 1000 1448 1900
(1 per phs)
650 (3 per phs)
3300 1900 (1 per phs)
650 (3 per phs)
4500 170M6466 4500 1900
900 1255 1600
(1 per phs)
550 (3 per phs)
2900 1600 (1 per phs)
550 (3 per phs)
3900 170M6466 3900 1700
20xE1K9
(2)
14 1100 1834 2300 (1 per phs)
800 (3 per phs)
4200 2300 (1 per phs)
800 (3 per phs)
5700 170M6466 5700 2400
1000 1448 1900 (1 per phs)
650 (3 per phs)
3200 1900 (1 per phs)
650 (3 per phs)
4500 170M6466 4500 1900
20xE2K2
(2)
14 1200 2172 2800 (1 per phs)
950 (3 per phs)
5000 2800 (1 per phs)
950 (3 per phs)
6700 170M6466 6700 2900
1100 1834 2300
(1 per phs)
800 (3 per phs)
4200 2300 (1 per phs)
800 (3 per phs)
5700 170M6466 5700 2400
(1)
20DE820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz.
(2)
Not available with 700S Control.
(3)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(4)
Maximum protection device size is the highest rated device that supplies drive protection.
(5)
These fuses and disconnect are supplied with AC input NEMA/UL Type 1 drives.
(6)
Inverse time breaker. Ratings shown are maximum.
(7)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(8)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip
settings must be set to US NEC code. Not to exceed 1300% FLA.
Drive
Catalog
Number
Frame
HP Rating
Input
Ratings
Dual Element Time Delay
Fuse Non-Time Delay Fuse
Bussmann Style
Semi-Conductor Fuse
Circuit
Breaker
(6)
Motor Circuit
Protector
(8)
ND HD Amps Min.
(3)
Max.
(4)
Min.
(3)
Max.
(4)
Max
(7)
Max.
Drive
Catalog
Number
Frame
kW Rating
Input
Ratings Dual Element Time Delay Fuse Non-Time Delay Fuse
Bussmann Style
Semi-Conductor Fuse
Circuit
Breaker
(6)
Motor Circuit
Protector
(8)
ND HD Amps Min.
(3)
Max.
(4)
Min.
(3)
Max.
(4)
Max.
(7)
Max.
20xF170 9 160 171 225 375 225 500 170M3819 500 250
132 145 200 300 200 500 170M3819 400 200
20xF208 9 200 210 275 450 275 600 170M3819 600 300
160 171 225 375 225 500 170M3819 500 250
20xF261 10 250 263 350 575 350 775 170M5813 750 350
200 210 275 450 275 600 170M5813 600 300
20xF325 10 315 327 425 725 425 950 170M5813 900 450
250 263 350 575 350 775 170M5813 750 400
20xF385 10 355 388 500 850 500 1100 170M5813 1100 500
315 327 425 725 425 950 170M5813 900 450
20xF416 10 400 419 525 900 525 1200 170M5813 1200 550
315 327 425 700 425 950 170M5813 900 450
20xF460 11 500 463 600 (1 per phs)
300 (2 per phs)
1000 600 (1 per phs)
300 (2 per phs)
1300 170M8547 1300 600
400 388 500 (1 per phs)
250 (2 per phs)
850 500 (1 per phs)
250 (2 per phs)
1100 170M8547 1100 500
20xF502 11 560 506 650
(1 per phs)
325 (2 per phs)
1100 650 (1 per phs)
325 (2 per phs)
1500 170M8547 1500 650
500 463 600
(1 per phs)
300 (2 per phs)
1000 600 (1 per phs)
300 (2 per phs)
1300 170M8547 1300 600
20xF590 11 580 594 750 (1 per phs)
375 (2 per phs)
1300 750 (1 per phs)
375 (2 per phs)
1700 170M5813 1700 800
500 506 650 (1 per phs)
325 (2 per phs)
1100 650 (1 per phs)
325 (2 per phs)
1500 170M5813 1500 700