Installation manual

A-18 Specifications
20xF650 12 630 655 850 (1 per phs)
425 (2 per phs)
1400 850 (1 per phs)
425 (2 per phs)
1900 170M5813 1900 900
560 594 750
(1 per phs)
375 (2 per phs)
1300 750 (1 per phs)
375 (2 per phs)
1700 170M5813 1700 800
20xF750 12 710 756 950 (1 per phs)
475 (2 per phs)
1600 950 (1 per phs)
475 (2 per phs)
2200 170M5813 2200 1000
630 655 850 (1 per phs)
425 (2 per phs)
1400 850 (1 per phs)
425 (2 per phs)
1900 170M5813 1900 900
20xF820
(1)
12 800 826 1100 (1 per phs)
550 (2 per phs)
1800 1100 (1 per phs)
550 (2 per phs)
2400 170M5813 2400 1100
630 655 850
(1 per phs)
425 (2 per phs)
1400 850 (1 per phs)
425 (2 per phs)
1900 170M5813 1900 900
20xF920 13 900 927 1200 (1 per phs)
600 (2 per phs)
2000 1200 (1 per phs)
600 (2 per phs)
2700 170M6466
(5)
2700 1200
800 826 1100 (1 per phs)
550 (2 per phs)
1800 1100 (1 per phs)
550 (2 per phs)
2400 170M6466
(5)
2400 1100
20xF1K0 13 1000 1038 1300
(1 per phs)
650 (2 per phs)
2300 1300 (1 per phs)
650 (2 per phs)
3000 170M6466
(5)
3000 1300
900 927 1200
(1 per phs)
600 (2 per phs)
2000 1200 (1 per phs)
600 (2 per phs)
2700 170M6466
(5)
2700 1200
20xF1K1 13 1100 1189 1500 (1 per phs)
750 (2 per phs)
2600 1500 (1 per phs)
750 (2 per phs)
3500 170M6466
(5)
3500 1500
1000 1038 1300 (1 per phs)
650 (2 per phs)
2300 1300 (1 per phs)
650 (2 per phs)
3000 170M6466
(5)
3000 1300
20xF1K5 14 1500 1511 1900
(1 per phs)
650 (3 per phs)
3300 1900 (1 per phs)
650 (3 per phs)
4500 170M6466 4500 1900
1300 1310 1700
(1 per phs)
575 (3 per phs)
2900 1700 (1 per phs)
575 (3 per phs)
3900 170M6466 3900 1700
20xF1K9
(2)
14 1800 1914 2400 (1 per phs)
800 (3 per phs)
4200 2400 (1 per phs)
800 (3 per phs)
5700 170M6466 5700 2400
1500 1511 1900 (1 per phs)
650 (3 per phs)
3200 1900 (1 per phs)
650 (3 per phs)
4500 170M6466 4500 1900
20xF2K2
(2)
14 2000 2267 2900 (1 per phs)
950 (3 per phs)
5000 2900 (1 per phs)
950 (3 per phs)
6700 170M6466 6700 2900
1800 1914 2400
(1 per phs)
800 (3 per phs)
4200 2400 (1 per phs)
800 (3 per phs)
5700 170M6466 5700 2400
(1)
20DF820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz.
(2)
Not available with 700S Control.
(3)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(4)
Maximum protection device size is the highest rated device that supplies drive protection.
(5)
These fuses and disconnect are supplied with AC input NEMA/UL Type 1 drives.
(6)
Inverse time breaker. Ratings shown are maximum.
(7)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(8)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip
settings must be set to US NEC code. Not to exceed 1300% FLA.
Drive
Catalog
Number
Frame
kW Rating
Input
Ratings Dual Element Time Delay Fuse Non-Time Delay Fuse
Bussmann Style
Semi-Conductor Fuse
Circuit
Breaker
(6)
Motor Circuit
Protector
(8)
ND HD Amps Min.
(3)
Max.
(4)
Min.
(3)
Max.
(4)
Max.
(7)
Max.