1-8 General Installation Information
Essential Requirements for CE Compliance
Conditions 1-6 listed below must be satisfied for PowerFlex drives to meet
the requirements of EN61800-3.
1. Standard PowerFlex 700H or 700S CE compatible Drive. For Frames 10
and up, the drive must also be installed in a suitable Rittal TS 8 (or
equivalent) enclosure.
2. Review important precautions/attention statements throughout this
manual before installing the drive.
3. Grounding as described on page 1-3
.
4. Output power, control (I/O) and signal wiring must be braided, shielded
cable with a coverage of 75% or better, metal conduit or equivalent
attenuation.
5. All shielded cables should terminate with the proper shielded connector.
6. Conditions in Table 1.C
.
Table 1.C PowerFlex EN61800-3 EMC Compatibility
Frame
Second Environment
Restrict Motor Cable to 30 m (98 ft.)
Any Drive and Option
9
10
11
12
13
14