Instructions for ATEX Approved PowerFlex 700H Drives in Group II Category (2) Applications with ATEX Approved Motors F-3
Table F.A Terminal Descriptions
Important:The drive will not run unless one of the following conditions is
met:
A wire must be installed in the hardware thermistor input
(X7-28 and X7-29) and the thermistor short circuit
supervisor jumper X10 must be installed in the OFF
position.
OR
A thermistor must be installed in the hardware thermistor
input (X7-28 and X7-29).
Term. Blk. No. Signal Description
X5 1 SD1+ Isolated Disable input 1 +24V +/-20% 10... 15mA
2 SD1– Virtual GND 1
3 SD2+ Isolated Disable input 2 +24V +/-20% 10... 15mA
4 SD2– Virtual GND 2
X2 21 Digital Out 1 - N.C. Max. Resistive Load:
240V ac / 30V dc - 1200VA, 150W
Max. Current: 5A, Min. Load: 10mA
Max. Inductive Load:
240V ac / 30V dc - 8400VA, 105W
Max. Current: 3.5A, Min. Load: 10mA
22 Digital Out 1 Common
23 Digital Out 1 - N.O.
X3 25 Digital Out 2 Common
26 Digital Out 2 N.O.
X7 28 TI1+ Thermistor input: R
trip
4.0 kΩ (PTC)
29 TI1–
21 22 23
25 26
1 2 3 4
28 29
ON OFF
X10
X5
X2
X3
X7