Installation manual

F-4 Instructions for ATEX Approved PowerFlex 700H Drives in Group II Category (2) Applications with ATEX Approved Motors
Figure 1 Wiring Example - Internal 24V Power Supply
Configuration
The PowerFlex 700H drive can be configure in one of five ways when using
the 20C-DG1 option board, each resulting in the drive being put into a Gate
Disabled state when digital inputs are removed or the thermistor is out of
range.
1. Gate Disable Fault (59):
Configured by setting bit 10 “Gate Disable” of parameter 238 [Fault
Config1].
If both digital inputs open, the drive output will be disabled and the
motor will coast to a stop. The drive HIM will display fault 59 “Gate
Disable”.
When the condition is cleared, the fault can be reset and the drive can be
restarted.
If only one digital input opens, the drive output will be disabled and the
motor will coast to a stop. Refer to Table F.B on page F-6
for a
description of drive conditions and actions.