Installation manual

1-10 General Installation Information
DC Input Precharge Control Wiring
If you are installing a DC input drive with a precharge interlock you must
make the following connections on the X50 terminal block from the
precharge circuit. Refer to Figure 1.1 on page 1-11
for additional
information.
Table 1.D X50 Terminal Block Connections
Table 1.E X50 Terminal Block Specifications
Table 1.F External Relay Contact Ratings
X50 Terminal Block Frame Terminal Description
9 1 Charge Relay Contact
2 Charge Relay Contact
5 Precharge Complete Signal (+24V DC)
6 Precharge Complete Signal (Common)
10, 11 & 13 3 Charge Relay Contact
4 Charge Relay Contact
1 Precharge Complete Signal (+24V DC)
2 Precharge Complete Signal (Common)
12 & 14 Power Module 1
3 Charge Relay Contact (Jumper to Power
Module 2 Terminal 4)
4 Charge Relay Contact
1 Precharge Complete Signal (+24V DC)
2 Precharge Complete Signal (Common)
Power Module 2
3 Charge Relay Contact
4 Charge Relay Contact (Jumper to Power
Module 1 Terminal 21)
1 Precharge Complete Signal (+24V DC)
2 Precharge Complete Signal (Common)
Wire Size Range
(1)
(1)
Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
Torque
Maximum Minimum Recommended
6.0 mm
2
(10 AWG) 1.0 mm
2
(18 AWG) 0.8 N•m (7.0 lb•in)
Load Resistance load (cos φ = 1)
Rated load 8 A at 250 VAC: 5 A at 30 VDC
Rated carry current 8 A
Max. switching voltage 250 VAC; 30 VDC, (400 VAC)
(1)
(1)
P level: λ60 = 0.1 x 10
–6
operations
Max. switching current AC 8 A; DC 5 A
Max. switching power 2,000 VA; 150 W
Failure rate (reference value) 5 VDC 10 mA (for gold plating 0.35 µ min.)