PowerFlex
®
700H Control Wiring 2-3
Figure 2.2 PowerFlex 700H I/O Terminal Blocks & Jumpers
I/O Terminal Blocks
Table 2.D I/O Terminal Block Specifications
No. Name Description
Wire Size Range
(2)
(2)
Maximum/minimum that the terminal block will accept - these are not recommendations.
Torque
Maximum Minimum Maximum Recommended
Analog I/O Analog I/O Signals 2.5 mm
2
(14 AWG)
0.5 mm
2
(22 AWG)
0.2 N-m
1.8 lb.-in.
0.2 N-m
1.8 lb.-in.
Digital Inputs Digital Input Signals 2.5 mm
2
(14 AWG)
0.5 mm
2
(22 AWG)
0.2 N-m
1.8 lb.-in.
0.2 N-m
1.8 lb.-in.
Digital Outputs
(1)
(1)
Refer to Appendix F, Instructions for ATEX Approved PowerFlex 700H Drives in Group II Category (2)
Applications with ATEX Approved Motors for more information on installing and configuring the Gate Disable
option board.
Digital Out Relays 2.5 mm
2
(14 AWG)
0.5 mm
2
(22 AWG)
0.5 N-m
4.5 lb.-in.
0.5 N-m
4.5 lb.-in.
I/O Terminal Blocks and Jumpers
J1 & J2
J3 & J4
J5