Installation manual

PowerFlex
®
700H Control Wiring 2-5
Figure 2.3 I/O Terminal Designations
No. Signal
Factory
Default
Description
Related
Parameter(s)
1 Analog Input 1 (–)
(1) (2)
Isolated
(3)
, bipolar, differential, 9 bit &
sign, 88k ohm input impedance. A
jumper (page 2-6
) selects: 0-10V, ±10V,
4-20mA. Default: 0-10V (Ri =200k),
4-20mA (Ri=100 ohm).
320 -
327
2 Analog Input 1 (+)
(1)
3 Analog Input 2 (–)
(1)
4 Analog Input 2 (+)
(1)
5 –10V Pot Reference 2k ohm minimum, 10 mA maximum load,
1% accuracy.
6 Pot Common (GND) For (+) and (–) 10V pot references.
7 +10V Pot Reference 2k ohm minimum, 10mA maximum load,
1% accuracy.
8 Analog Output 1 (+)
(2)
Bipolar (current out is not bipolar), 9 bit &
sign, 2k ohm minimum load. A jumper
(see page 2-6
) selects: 0-10V, ±10V,
4-20mA.
340 -
347
9 Analog Output Common
10 Analog Output 2 (+)
11 Digital Input 1 Stop - CF 115V ac, 50/60 Hz - Opto isolated
Low State: less than 30V ac
High State: greater than 40V ac
24V dc
- Opto isolated (250V)
Low State: less than 5V dc
High State: greater than 20V dc
11.2 mA DC
Enable
: Digital Input 6 is jumper
selectable for HW Enable.
On-Time: < 16.7ms, Off-Time < 1ms
361 -
366
12 Digital Input 2 Start
13 Digital Input 3 Auto/Man
14 Digital Input 4 Speed Sel 1
15 Digital Input 5 Speed Sel 2
16 Digital Input 6/Hardware
Enable, see pg. 2-6
Speed Sel 3
17
18
Digital Input Common Allows source or sink operation.
Terminals 17/18 & 19 can also be used
to provide backup power to DPI and
control devices.
19 +24VDC
(4)
Drive supplied logic input power.
20 24V Common
(4)
Common for internal power supply.
21 Digital Output 1 – N.C.
(5)
Fault Max. Resistive Load:
240V ac/30V dc – 1200VA, 150W
Max. Current: 5A, Min. Load: 10mA
Max. Inductive Load
:
240V ac/30V dc – 840VA, 105W
Max. Current: 3.5A, Min. Load: 10mA
380 -
391
22 Digital Output 1 Common
23 Digital Output 1 – N.O.
(5)
NOT Fault
24 Digital Output 2 – N.C.
(5)
NOT Run
25 Digital Output 2/3 Com.
26 Digital Output 3 – N.O.
(5)
Run
(1)
Important: Input must be configured with a jumper. Drive damage may occur if jumper is not installed properly. Refer
to page 2-6
.
(2)
These inputs/outputs are dependant on a number of parameters (see “Related Parameters” column in table).
(3)
Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high
common mode immunity.
(4)
150mA maximum load. Not present on 115V versions. Can be used to provide control power from an external 24V
source when main power is not applied. Refer to page 2-6
.
(5)
Contacts in un-powered state. Any relay programmed as Fault or Alarm will energize (pick up) when power is applied
to drive and de-energize (drop out) when a fault or alarm exists. Relays selected for other functions will energize only
when that condition exists and will de-energize when condition is removed.
1
10
20
21