2-12 PowerFlex
®
700H Control Wiring
PLC = Auto, Terminal Block = Manual
A process is run by a PLC when in Auto mode and requires manual control
from an analog potentiometer wired to the drive terminal block. The auto
speed reference is issued by the PLC through a communications module
installed in the drive. Since the internal communications is designated as
Port 5, [Speed Ref A Sel] is set to “DPI Port 5” with the drive running from
the Auto source. Since the Manual speed reference is issued by an analog
input (“Analog In 1 or 2”), parameter 96 [TB Man Ref Sel] is set to the
same input. To switch between Auto and Manual, parameter 364 [Digital
In4 Sel] is set to “Auto/ Manual”.
Attain Manual Control
Close the digital input.
With the input closed, the speed command comes from the pot.
Release to Auto Control
Open the digital input.
With the input open, the speed command returns to the PLC.
Auto/Manual Notes
1. Manual control is exclusive. If a HIM or Terminal Block takes manual
control, no other device can take manual control until the controlling
device releases manual control.
2. If a HIM has manual control and power is removed from the drive, the
drive will return to Auto mode when power is reapplied.
3. Parameter 192 [Save HIM Ref] can enable manual mode to allow starts
and jogs from the HIM in 2-wire mode.