Installation manual

Control Wiring for PowerFlex 700S Drives with Phase II Control 4-5
Table G TB2 Terminals
Terminal Signal
Factory
Default Description
1 24V DC Common (-) NA Drive supplied 24V DC logic input power
Rating: 300 mA maximum load
2 24V DC Source (+) NA
3 Digital Output 1 24V DC Open Collector (sinking logic)
Rating: Internal Source = 150 mA max.
External Source = 750 mA
4 Digital Output 1/2 Com NA Common for Digital Output 1 & 2
5 Digital Output 2 24V DC Open Collector (sinking logic)
Rating: Internal Source = 150 mA max.
External Source = 750 mA
6 Relay Output 3 (NC) Relay contact output
Rating: 115V AC or 24V DC = 2 A max.
Inductive/Resistive
7 Relay Output 3 Com NA
8 Relay Output 3 (NO)
9 Digital Input 1-3 Com NA Common for Digital Inputs 1-3
10 Digital Input 1 High speed 12V or 24V DC
(1)
, sinking
Load:15 mA at 24V DC
11 Digital Input 2
12 Digital Input 3 Load:15 mA at 24V DC sourcing
13 Digital Input 4-6 Com NA Common for Digital Inputs 4-6
14 Digital Input 4 Load: 10 mA at 24V DC sinking/sourcing
Load: 7.5 mA at 115V AC
Note: The 115 VAC Digital Inputs can withstand 2
milliamps of leakage current without turning on. If an
output device has a leakage current greater than 2
milliamps a burden resistor is required. A 68.1K ohm
resistor with a 0.5 watt rating should be used to keep
the 115 VAC output below 2 milliamps.
15 Digital Input 5
16 Digital Input 6 HW Enable
(1)
Digital Inputs 1 and 2 are configured for 12V or 24V DC via DIP switches S3-1 and S3-2, respectively. 24V DC is the default setting.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16