Installation manual

Control Wiring for PowerFlex 700S Drives with Phase II Control 4-11
DIP Switch Settings
Figure 3 Main Control Board Dip Switches
Table E Switch Settings
!
ATTENTION: The DIP switches for Digital Inputs 4 - 6 are set
to 24V DC at the factory. If you are running a 115V AC input
application, the switches must be set as indicated below before
applying power to the drive or damage to the Main Control board
may occur.
S1
12
FRONT
TOP VIEW
SIDE VIEW
Up = Open = Off
Down = Closed = On
SWITCH S5
FRONT
TOP VIEW
SIDE VIEW
Up = Open = Off
Down = Closed = On
SWITCH S2
12
34
12
FRONT
TOP VIEW
SIDE VIEW
Up = Open = Off
Down = Closed = On
SWITCH S3
12
FRONT
TOP VIEW
SIDE VIEW
Up = Open = Off
Down = Closed = On
SWITCH S4
= HW Enable
= No HW Enable
JUMPER P22
12
34
12
34
Function Default Switch Open Closed Notes
Configuring Digital
Input 6 for Hardware
Enable (HW Enbl)
pin 2-4
HW Enbl
P22
Jumper
pin 2-4
HW Enbl
pin 1-3
No Enbl
No Jmpr = HW Enbl
Analog Input 1 Voltage S5-2 Voltage Current Change with Power Off
Analog Input 2 Voltage S5-1 Voltage Current Change with Power Off
Digital Inputs 4-6
Voltage
24V DC S4-1,
S4-2
115V AC 24V DC Change with Power Off
Digital Input 1
Voltage
24V DC S3-1 24V DC 12V DC Change with Power Off
Digital Input 2
Voltage
24V DC S3-2 24V DC 12V DC Change with Power Off