Installation manual

Frame 9 Installation 6-5
Power Wiring
Table 6.A Frame 9 Power Terminal Specifications
Figure 6.2 Terminal Locations and Power Terminal Block
No. Name Description
Wire Size Range
(1)
Torque
Maximum Minimum Recommended
Input Power Terminal Block
(2)
L1, L2, L3
Input power 185.0 mm
2
(350 MCM)
95.0 mm
2
(4/0 AWG)
40 N•m
(354 lb•in)
Output Power Terminal Block
(2)
U/T1, V/T2, W/T3
Motor connections 185.0 mm
2
(350 MCM)
95.0 mm
2
(4/0 AWG)
40 N•m
(354 lb•in)
SHLD Terminal, PE, Motor Ground Terminating point for wiring shields 95.0 mm
2
(4/0 AWG)
5.0 mm2
(10 AWG)
22 N•m
(195 lb•in)
DC Bus
(3)
(2 Terminals; DC–, DC+)
DC input or external brake resistor
(Internal Brake option not provided - Refer to Frame
9 DC Bus/Brake Connections on page 6-6.)
185.0 mm
2
(350 MCM)
95.0 mm
2
(4/0 AWG)
40 N•m
(354 lb•in)
DC Bus w/Brake
(3)
(3 Terminals; DC–, DC+/R+, R–)
DC input/internal brake
(Internal Brake option is provided - Refer to Frame 9
DC Bus/Brake Connections on page 6-6.)
185.0 mm
2
(350 MCM)
95.0 mm
2
(4/0 AWG)
40 N•m
(354 lb•in)
Cable Clamp for Shield
(1)
Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
(2)
Do Not exceed maximum wire size. Parallel connections may be required.
(3)
DC terminal and brake lugs can be removed.
D
C
D
C
+
/
R
+
R
DC –
DC+/R+
R–
L1
AC Line Input Power To Motor Leads
L2 L3 L1 L2 L3 U/T1 V/T2 W/T3 U/T1 V/T2 W/T3
DC-, DC+/R+, R-
terminals shown with
protective cover removed.