Installation manual

7-2 Frame 10 Installation
Figure 7.2 Enclosure Code B (NEMA/UL Type 1, IP21) and K (NEMA/UL Type 1, IP21
w/Conformal Coat)
Operating Temperatures
Frame 10 drives require a minimum of 2600 m
3
/h (1530 cfm) of cooling air.
200 mm
(7.87 in.) Min.
Powerful Performance, Flexible Control.
838 mm
(33.0 in.) Min.
PowerFlex Drive Voltage Class Amp Rating
Surrounding Air Temperature
Normal Duty Heavy Duty
700H & 700S 400/480V AC
(540/650V DC)
All 0 to 40° C
(32 to 104° F)
0 to 40° C
(32 to 104° F)
600/690V AC
(810/932V DC)
261, 325, 385 0 to 40° C
(32 to 104° F)
0 to 40° C
(32 to 104° F)
600/690V AC
(810/932V DC)
416 0 to 35° C
(32 to 95° F)
0 to 40° C
(32 to 104° F)