Installation manual

Frame 10 Installation 7-13
Disconnect the Small Capacitors from the Input Terminals
Follow the lettered steps below to disconnect the small capacitors from the
input terminals:
Important:Do not re-install the capacitor leads.
Task Description
Remove the screws and lock washers that secure each of the three capacitor supply wires
to the input power terminals.
Insulate the capacitor leads and leave disconnected.
Install and tighten the screws and lock washers only.
A
B
C
L1
L2
L3
Important:It is not necessary to remove the power
wiring from the terminals in order to
insulate the capacitor leads.
Capacitor
Insulator
Capacitor lead -
leave disconnected
Input power terminal
A
B
C
Front View of Input
Power Terminals
Side View of Input
Power Terminals