Specifications

Publication GMC-SG001E-EN-P June 2001
4-24 1394 Drive System Family
User-Supplied Input Fusing Specifications
The following section contains user-supplied input fusing specifications for the 1394 system and 1394
SERCOS interface system.
User-Supplied 24V Logic Input Power Specifications
The following section contains user-supplied 24V logic input power for the 1394 system and 1394 SERCOS
interface system.
Note: The power supply must be rated for 15A or greater inrush current upon power up.
Input Transformer Specifications for 24V Control Power
The following section contains 24V input transformer specifications for the 1394 system and 1394 SERCOS
interface system
.
Note: If the input volt-amperes is more than 350 VA, adjust the load regulation to make the transformer
leakage the same as or greater than the 250 VA transformer with 2% regulation.
System Fuse Description Rating
1394-SJT05 systems Series A and B Bussmann FRS-R-20A or equivalent 600V AC, 20A
1394C-SJT05 systems Series C
Bussmann KTK-R-20 or equivalent 600V AC, 20A
Bussmann LPJ-SP 20 or equivalent 600V AC, 20A
1394-SJT10 systems Series A and B Bussmann FRS-R-30A or equivalent 600V AC, 30A
1394C-SJT10 systems Series C
Bussmann KTK-R-30 or equivalent 600V AC, 30A
Bussmann LPJ-SP 30 or equivalent 600V AC, 30A
1394x-SJT22 systems
Bussmann FRS-R-35 or equivalent 600V AC, 35A
Bussmann LPS-RK-SP 40 or equivalent 600V AC, 40A
Bussmann LPJ-SP 45 or equivalent 600V AC, 45A
Specifications
24V Logic Input
Voltage
Frequency
Current
Recommended Fuse
Axis
Maximum User-Supplied
Power Supply
19-28V AC RMS,
single phase
50/60 Hz
1 axis 3.5A
Bussmann MDA-15
or equivalent
2 axis 4.4A
18.75-31.25V DC
3 axis 5.2A
4 axis 6.0A
Specification
Description
480V system 360V system
Input volt-amperes 200 to 259 VA 200 to 259 VA
Input voltage 480V RMS 360V RMS
Output voltage 24V RMS 24V RMS
Load regulation 2 to 5% 2 to 5%