Setup guide

Chapter 3 Driver and Protocol Objects
©
Automationdirect.com 3-19 Object Reference Manual
5136-SD cards support different sets of valid memory addresses. See the
documentation that shipped with the card for details.
Invalid node address for card: xx
Node addresses must be between 0 and 63 decimal.
Invalid port number for SS card: 0xPPP
The port number specified for the 5136-SD card is invalid. See the
documentation that shipped with the card for the list of valid port addresses.
Invalid port or memory address
Lookout
Direct
was unable to write to the 5136-SD card physical memory.
This could be due to either an invalid port or memory address or to a faulty
or improperly seated card.
KT card failed to find resources
KT card receive mailbox is in an invalid state
KT card send mailbox is in an invalid state
You will probably never see one of these alarms. If you do, call National
Instruments and ask for technical support.
KT card dual-ported memory test failed at location xxxx
The interface card failed a memory test when it was first powered on. The
memory test reads, writes and rereads the dual-ported memory to ensure
memory access by the card. Verify that the card is configured for the
memory address that you specified. Verify that your memory manager
(like EMM386) excludes the appropriate portion of memory. Verify that
your card is not trying to use the same memory location as another card.
You may need to restart the card by calling up the AB object definition
dialog box and selecting OK. If that does not work try rebooting the
computer. Other causes can include memory conflicts, a bad interface
card, or a misbehaving driver.
KT card CTC test timed out
KT card CTC test failed with status code xx
The interface card failed the Counter Timer Circuit test when it was first
powered on. This test verifies proper functionality of the card timer and
counter modes over all CTC channels. You may need to restart, reseat,
or replace the interface card.