2-10 Configurable FLEX I/O Analog Module Features
Table 2.4 1794-OE8H Data Formats
Data 
Format
Format Resolution Full 
Output 
Range
Module Data Processing Data Table Value 
(Interpretation)
Count 
per mA
Analog Fault 
State
0mA as 
0…20 mA
0.1% of 
0…20 mA
0…22 mA 0…22000 
(0…22.000 mA)
1000 Min=0 mA 
Max=22 mA 
Hold 
last=hold 
50%=11 mA
1 % as 
0…20 mA
0.2% of 
0…20 mA
0…22 mA 0…11000 
(0…110.00%)
500 Min=0 mA 
Max=22 mA 
Hold 
last=hold 
50%=11 mA
2 Not Assigned
3 Unsigned 
integer as 
0…20 mA
0.03% of 
0…20 mA
0…20 mA 0…65535    
(0…22 mA)
3276 Min=0 mA 
Max=20 mA 
Hold 
last=hold 
50%=10 mA
4mA as 
4…20 mA
0.1% of 
4…20 mA
2…22 mA 2000…22000 
(2.000…22.000 
mA)
1000 Min=2 mA 
Max=22 mA 
Hold 
last=hold 
50%=12 mA
5 4…20 mA — 4…20 mA Not assigned  —
——
6 4…20 mA 4…20 mA
7 Unsigned 
integer as 
4…20 mA
0.03% of 
4…20 mA
4…20 mA 0…65535    
(4…20 mA)
4095 Min=4 mA 
Max=20 mA 
Hold 
last=hold 
50%=12 mA
8 Not Assigned
9
Output = 
datatable
(
1000
)
Output = 20
datatable
(
10000
)
Output = 20
datatable
(
65535
)
Output = 
datatable
(
1000
)
Output = 16
datatable
(
65535
)
+ 4