131 Publication 1734-UM011D-EN-P - May 2011
Appendix
D
Quick Start
What This Appendix
Contains
In this quick start, you learn how to use the 1734-AENT adapter with a
ControlLogix controller for EtherNet/IP systems.
Necessary Prerequisites
Before you begin this quick start, make sure the following conditions are in
place.
The ControlLogix controller and RSLogix software version must be
version 11 or later.
The 1756-ENBT module must be revision 2.3 or later.
The 1734 POINT I/O modules must be series C (except for the
1734-232ASC modules, which can be series A).
The recommended RPIs are being used: Digital = 10 ms or higher,
Analog and Specialty = 50 ms or higher.
The 1734-AENT POINT I/O adapter is a child to a local 1756-ENBT
module.
IMPORTANT
This quick start contains a simple set of steps and
reminders that will help you avoid errors when you are
configuring your POINT I/O system for and
EtherNet/IP network.
ATTENTION
You must use series C POINT I/O modules with the
1734-AENT adapter. Series A or B POINT I/O modules will
not work with this adapter.