User manual

Publication 1734-UM011D-EN-P - May 2011
Quick Start 137
If you downloaded the offline configuration into the module and
then realize that you must modify any of the module’s configuration
parameters, then the preferred way to make these changes online is to
go to the Module Connection tab and inhibit the module, apply the
changes, and then uninhibit the module. Doing this breaks the
connection, causing the configuration information to be downloaded
right after the connection is made.
6. Right-click the 1734-AENT adapter and select Properties.
7. Click the Connection tab.
You see the following message:
The module is faulted because, even though you set up the adapters
POINT I/O chassis size to the actual number of the modules plus the
adapter, the adapter still remembers the size of 1 (the factory default
value) until you reset this size manually. This option is available only
online.
8. Click the Chassis Size tab.
9. Click the Set Chassis Size in Module button and set the chassis size in
the adapter.
Remember to inhibit and unhibit the module for this to take effect.
IMPORTANT
Switching the controller from Program to Run mode does
not change the module connection status and does not
re-send module configuration data.
We highly recommend that you use the inhibit/uninhibit
process and avoid power cycling.