Publication 1756-RM093F-EN-P - January 2010 59
Safety Application Development Chapter 6
The steps below illustrate one method for confirming the project.
1. With the controller in Program mode, save the project.
2. Answer Yes to the Upload Tag Values prompt.
3. With RSLogix 5000 software offline, save the project with a new
name, such as Offlineprojectname.ACD, where projectname is
the name of your project.
This is the new tested master project file.
4. Close the project.
5. Move the original project archive file out of this directory.
You can delete this file or store it in an archival location. This
step is required because if RSLogix 5000 software finds the
projectname.ACD in this directory, it will correlate it with the
controller project and will not perform an actual upload.
6. With the controller still in Program mode, upload the project
from the controller.
7. Save the uploaded project as Onlineprojectname.ACD, where
projectname is the name of your project.
8. Answer Yes to the Upload Tag Values prompt.
9. Invoke another instance of RSLogix 5000 software and open the
project named Offlineprojectname.ACD.
10. Use the two instances of RSLogix 5000 software to compare the
following:
All of the properties of the GuardLogix controller and CIP
Safety I/O modules
All of the properties of the safety task, safety programs and
safety routines
All of the logic in the safety routines
TIP
RSLogix 5000 software features a Program Compare utility that
may be helpful in identifying changed safety components, but it
must not be used in place of a manual compare. (Compare the
offlineprojectname.acd to onlineprojectname.acd.)