User manual

Publication 1734-UM011A-EN-P - February 2004
C-38 1734-POINT I/O Module/RSLogix 5000 Controller Tag Reference
1734-232ASC
1 Channel ASCII Interface Module
Configuration Data Data Type Default
Value
Valid Data Values
Serial Character Format
(ASCII Format:
Data Bits / Parity / Stop)
SINT 0 0=7N2
1=7E1
2=7O1
3=8N1
4=8N2
5=8E1
6=8O1
7=7E2
8=7O2
Serial Comm Speed
(Baud Rate of the Serial Port)
SINT 0 0=9600
1=1200
2=2400
3=4800
4=19.2K
5=38.4K
Max Receive Characters SINT 20 -128 to +127 (0 - 128)
Receive Start Delimiter Mode SINT 0 0=No Start Delimiter
1=Exclude Start Delimiter
2=Include Start Delimiter
Receive Start Delimiter Character SINT 58
(0x3A)
Any Valid ASCII Character
(Default is Colon [:])
Receive Record End Mode SINT 2 0=No End Delimiter
1=Exclude End Delimiter
2=Include End Delimiter
Receive End Delimiter SINT 13
(0x0d)
Any Valid ASCII Character
(Default is Carr. Return)
Receive String Data Type SINT 1 0=Array
1=Short String
2=String
Pad Mode SINT 1 0=Pad Mode Disabled
1=Pad Mode Enabled
Pad Character SINT 0
(0x00)
Any Valid ASCII Character
(Default is NULL)
Receive Swap Mode SINT 0 0=Disabled
1=16-bit Swap Enabled
2=24-bit Swap Enabled
3=32-bit Swap Enabled
DeviceNet Handshake Mode SINT 1 0=Master/Slave handshake
1=Produce Immediate
Max Transmit Characters SINT 20 -128 to +127 (0 - 128)