User manual

1 Publication 1734-UM011A-EN-P - February 2004
Appendix
D
1734-AENT Quick Start
What’s In This Appendix?
In this quick start, you will learn how to use the 1734-AENT with a
ControlLogix processor for EtherNet/IP.
Necessary Pre-requisites
Before you began this quick start, make sure the following conditions are in
place.
The ControlLogix Controller and the RSLogix software version must be
version 11 or higher.
The 1756-ENBT module must be version 2.3 or higher.
The 1734 POINT I/O modules must be Series C (except for the
1734-232ASC modules, which can be Series A).
The recommended RPIs are being used: Discrete = 10 ms or higher,
Analog and Specialty = 50 ms or higher.
The 1734-AENT POINT I/O adapter is a child to a local 1756-ENBT
module.
IMPORTANT
This quick start contains a simple set of steps and
reminders that will help you avoid errors when you are
configuring your POINT I/O system for EtherNet/IP.
ATTENTION
You must use Series C POINT I/O modules with the
1734-AENT adapter. Series A or B POINT I/O
modules will not work with this adapter.