User manual

Publication 1734-UM011A-EN-P - February 2004
4-18 Configure the 1734-AENT for Direct Connection in RSLogix 5000
9. Click OK.
At this point, your PointBus status LED should be solid green. All the
yellow triangles in your I/O configuration should be gone.
Configure the 1734-AENT
with Fixed IP Address
To configure the 1734-AENT with a fixed IP address to prevent the adapter
from ceasing to communicate with the ControlLogix controller:
1. Click on the Port Configuration tab in the 1734-AENT properties
window.
2. Click the Enable DHCP box so that there is not a check mark in the box.
3. Click the Set button.
4. Read and acknowledge the warning.
5. Click OK.
6. Click the Refresh button to verify the changes.